8
Refrigerant Flow Diagram - WQRC 524 to 1604 - R410A
COMPONENTS
1 Compressor
4 Drier filter
5 Sight glass
6 Mechanical expansion valve
7 Indoor heat exchanger
9 Electronic expansion valve
11 Globe valve
12 Liquid receiver
13 Solenoid valve
SAFETY/CONTROL DEVICES
A High pressure switch (40,5 bar)
B Low pressure switch (1,5 bar)
AT High pressure transducer
BT Low pressure transducer
C Water differential pressure switch (50 mbar)
E Outlet water temperature sensor
F Inlet water temperature sensor
G Inlet water temperature sensor
H Outlet water temperature sensor
I Ped pressure relief valve (45 bar)
S 5/16” Shrader connection (service only)
Pipe connection with Shrader valve
465
S
MECHANICAL EXPANSION
VALVE (STANDARD)
G
H
7
C
ST
EEV
CONTROL
BT
ELECTRONICAL EXPANSION
VALVE (OPTIONAL)
459
OIL EQUAL.
1
I
AT
S
ONLY SIZE 904-1604
BAA
S
11
11 12 13
I