Electrical Data - SyScroll 20-35 Air
400V/3/50Hz
NOMINAL MAXIMUM
P
NOM-CPS
I
NOM-CPS
P
MAX-CPS
I
MAX-CPS
FLA I
STARTUP-CPS
LRA PFC (NOM) PFC*
Size kW A kW A A
20 6,3 12 8,6 16 101 0,78 > 0.90
25 7,1 13 10,2 21 111 0,80 > 0.90
30 8,7 15 11,9 22 118 0,83 > 0.90
35 11,3 19 14,8 31 140 0,85 > 0.90
Compressor Data
230V/1/50Hz P
MAX-FANS
I
MAX-FANS
FLA
Size kW A
20 0,60 2,60
25 0,60 2,60
30 0,60 2,60
35 0,60 2,60
Fans Data
400V/3/50Hz P
MAX-PUMP
I
MAX-PUMP
FLA
Size kW A
20 0,72 1,30
25 0,72 1,30
30 0,72 1,30
35 0,72 1,30
Pumps Data
400V/3+N/50Hz
STD unit with pump
20 25 30 35
Power input (kW)
Nominal
Maximum
8 8 10 13
10 12 13 16
Current input (A)
Nominal
Maximum
16 17 19 23
20 25 26 35
Start-up current (A)
105 115 122 144
Start-up current (A)** 75 82 87 102
* Power factor correction capacitor option installed.
** Soft-starter option installed.
Acoustic Data - SyScroll 20-35 Air
Size
Octave Band (Hz)
Sound Power
Level dB(A)
Sound Pressure
Level* dB(A)
63 125 250 500 1000 2000 4000 8000
Sound Power Level (dB)
20
73 71 75 71 68 63 55 48 73 41
25
74 72 76 72 69 64 56 48 74 42
30 74 72 76 72 69 64 56 48 74 42
35
75 73 77 73 70 65 57 49 75 43
* Sound pressure level at 10 m.- Values refers to ISO Standard 3744 with parallepiped shape.