SMOKE CONTROL DAMPERS 1396 - CPD - 0058 Round DKIR1 and Rectangular DKIS1 ORIGINAL INSTALLATION, OPERATION AND MAINTENANCE MANUAL EVERY SMOKE DAMPER NEEDS TO BE INSTALLED IN ACCORDANCE WITH THIS MANUAL!
/8 | PP-52_201504 | DKIR1 & DKIS1 Fig. 1: Installatin of the round smoke damper DKIR1 onto and into the duct running through the vertical supporting construction (ved - see the fire resistivity on the page 3) Fig.
DKIR1 & DKIS1 AC 230 V 1 2 3 4 5 6 7 M The device contains no parts which can be replaced or repaired by the user.
/8 | PP-52_201504 | DKIR1 & DKIS1 8,8×11,8 R1 L=360 R2 W1 W×H (W+80)×(H+80) Fig. 10: Dimensions of the rectangular smoke damper with W > 1200 mm up to 1500 × 800 mm NOTE: These smoke dampers have flanges width 40 mm. Warnings Some damper parts can have sharp edges – therefore it is necessary to use gloves during damper installation and manipulation.
DKIR1 & DKIS1 trained by the manufacturer. Before putting dampers into service after installation (and in subsequent periodic inspections) visual inspection and functional test must be conducted. After the visual inspection and functional test a record must be made into operational diary (page 6). 2 Operating and Maintenance 2.1 The damper operation After installation, the damper must be set up into the operating position - closed. By connecting a power source to activate the actuator the blade shall move.
/8 | PP-52_201504 | DKIR1 & DKIS1 OPERATING DIARY Activation of the damper Date Description of found defects and date of the following inspection after deficiencies elimination Inspection technician‘s signature Periodic damper inspection - at least once in 12 months Date Description of found defects and date of the following inspection after deficiencies elimination Inspection technician‘s signature
DKIR1 & DKIS1 | PP-52_201504 | Periodic damper inspections - at least once in 12 months Date Description of found defects and date of the following inspection after deficiencies elimination Inspection technician‘s signature 7/8
DKIR1 & DKIS1 12 1396 IMOS-Systemair 90043 Kalinkovo 146, Slovakia 1396 - CPD - 0058 EN 12101-8 Smoke damper: round DKIR1-DN, rectangular DKIS1-WxH Operational reliability: ‐ cycling 10 200 cycles - passed Fire resistance: E600120(ved i↔o)S500C10000AAsingle or E600120(ved i↔o)S1500C10000AAsingle (see the page 3) - maintenan. of t.