To override the ECO mode, the Fdi parameter must be set to 0 (Eco)
Caution
16 SYSLOGIC
6. PARAMETER TABLE MODBUS
After modication of MODBUS address, the new Adr” value become actual only if MB2 module (586507
part number) have been properly recognized.
Without MB2 module the valid MODBUS address is always the default one: 1.
PAR. Description M.U. Min Max Default
MODBUS
Modiable via
MRC/WRC
Type Gain Adress*
P00 Septpoint differential °C / °F 0.2 2 0.5 UW 0.1 40002
P01 Auto-changeover deadband °C / °F 1 5 3 UW 0.1 40003
P02
Temperature unit:
0 = Celsius
1 = Farenheit
enum 0 1 0 enum 1 40023
P05 Offset air temperature (heating mode) °C / °F -5 5 0 SW 0.1 40004
P06 Offset air temperature (cooling mode) °C / °F -5 5 0 SW 0.1 40005
Pdi
Digital input polarity 1
0 = Normally open
1 = Normally closed
enum 0 1 1 B 1 40024
P09 Temperature setpoint for electrical heater °C / °F 30 122 40 UW 0.1 40006
P10 Temperature hysteresis for electrical heater °C / °F 0.4 2 2 UW 0.1 40007
P11 Temperature setpoint °C / °F P23 P24 21 UW 0.1 40008
P18 Reduced mode offset °C / °F 1 15 3 UW 0.1 40009
P19 Fan ON time in heating mode min 0 900 1 UW 1 40010
P20 Fan OFF time in heating mode min 0 900 20 UW 1 40011
P21 Fan ON time in cooling mode min 0 900 1 UW 1 40012
P22 Fan OFF time in cooling mode min 0 900 20 UW 1 40013
P29 Water valve OFF time sec 1 900 600 UW 1 40014
P30 Water valve ON time sec 0 900 240 UW 1 40015
Fdi
DI1 configuration:
0 = Eco mode
1 = ON/OFF
enum 0 1 1 UW 1 40025
P80 Set voltage EC motor - low speed V/100 0 999 330 UW 1 40016
P81 Set voltage EC motor - medium speed V/100 0 999 660 UW 1 40017
P82 Set voltage EC motor - high speed V/100 0 999 990 UW 1 40018
F-Adr Slave address - 1 247 1 UW 1 40020
F-bAU
Baud rate:
0 = 9600
1 = 19200
2 = 38400
- 0 2 0 UW 1 40021
F-PtY
Parity:
0 = none
1 = odd
2 = even
- 0 2 0 UW 1 40022
AtS
Reference temperature control probe:
0 = Aib (Entering air temperature)
1 = AiL (WRC/MRC/IR receiver)
2 = mean (AiL/Aib)
3 = heating: AiL, cooling mean
enum 0 3 1 UW 0.1 40027
FaN
Ventilation speed:
1 = MIN
2 = MED
3 = MAX
4 = AUTO
enum 1 4 1 UW 1 40019
ECO
Override the ECO mode
0 = eco OFF
1 = eco ON
enum 0 1 0 UW 1 40028
6.1. CONFIGURATION PARAMETERS
* Addresses are of the holding registers type.