SYSCOIL COMFORT Engineering Data Manual (EDM SCC 01 S 2GB)

SYSCOIL COMFORT
16
Technical Data
SYSCOIL COMFORT with EC motor
(1) Nominal conditions : Air : 27°C/19°C wet bulb (nominal HS
airow) - Chilled water : 7°C/12°C.
(2) Nominal conditions : Air : 20°C (nominal HS airow)
Hot water :
2 pipes - 45°C/40°C
4 pipes - 65°C/55°C
(3) Pressure loss by corresponding nominal ow.
(4) The sound pressure levels Lp are based on (NR)
characteristics of a room having volume of 100 m
3
with
reverberation of 0.5 seconds.
SCC50 SCC60 SCC70 SCC80
V1 V3 V5 V1 V3 V5 V1 V3 V5 V1 V3 V5
Capacites - 2 pipes
Cooling
(1)
Total cooling capacity KW 1.34 3.57 4.98 1.98 4.45 5.24 2.55 5.56 6.55 4.59 6.13 8.36
Sensible capacity KW 1.05 2.70 3.70 1.35 3.51 4.02 1.91 4.10 4.96 3.32 4.51 6.28
Water ow l/h 231 615 858 341 767 903 439 958 1 128 791 1 056 1 440
Water pressure drop
(3)
kPa 4.86 28.70 53.90 7.75 35.80 49.00 2.72 12.60 17.50 11.80 19.50 34.20
Heating
(2)
Heating capacity KW 1.38 3.89 5.19 1.95 4.93 5.82 3.05 5.81 7.17 4.63 6.39 9.28
Water ow l/h 238 670 894 336 849 1 002 525 1 001 1 235 798 1 101 1 598
Water pressure drop
(3)
kPa 3.79 25.70 44.60 12.20 70.70 97.50 3.87 13.80 20.90 11.90 21.00 41.50
Capacites - 4 pipes
Cooling
(1)
Total cooling capacity KW 1.17 3.45 4.39 1.69 3.9 4.69 2.44 4.88 6.06 4.44 5.86 9.07
Sensible capacity KW 0.92 2.61 3.28 1.12 3.05 3.63 1.83 3.61 4.53 3.2 4.31 6.84
Water ow l/h 202 594 756 291 672 808 420 841 1 044 765 1 009 1 562
Water pressure drop
(3)
kPa 2.32 16.20 25.60 4.59 22.00 31.40 3.21 12.30 18.80 18.80 30.60 67.20
Heating
(2)
Heating capacity KW 2.18 3.34 4.10 1.81 4.05 4.81 3.45 4.67 5.53 5.74 7.99 12.90
Water ow l/h 188 288 353 156 349 414 297 402 476 494 688 1 111
Water pressure drop
(3)
kPa 6.53 13.60 19.60 6.10 22.90 30.90 32.20 53.90 72.40 19.20 34.50 83.10
Sound levels - 2 pipes
Sound power level dB(A) 30 51 57 32 54 58 40 54 59 51 56 64
Sound pressure level
(4)
dB(A) 21 42 48 23 45 49 31 45 50 42 47 55
NR
(4)
dB(A) 16 37 43 18 40 44 26 40 45 37 42 50
Sound levels - 4 pipes
Sound power level dB(A) 30 51 57 32 54 58 40 54 59 51 56 64
Sound pressure level
(4)
dB(A) 21 42 48 23 45 49 31 45 50 42 47 55
NR
(4)
dB(A) 16 37 43 18 40 44 26 40 45 37 42 50
Fans
Number 2 2 2 3
2 pipes
Setpoint voltage V 2 7 10 2 7 10 4 8 10 3 4.1 6.4
Air ow m³/h 203 577 816 245 737 912 350 850 1 050 685 927 1 398
4 pipes
Setpoint voltage V 2 7 10 2 7 10 4 8 10 3 4.1 6.4
Air ow m³/h 185 587 755 205 668 845 329 798 989 660 884 1 548
Filter G2
Electrical data
Power supply V/Ph/Hz 230V/1~/50Hz - 230V/1~/60Hz
Absorbed power - 2 pipes W 4 23 46 4 30 54 11 44 77 23 42 108
Absorbed power - 4 pipes W 4 23 44 4 28 52 11 43 75 22 41 116
Electrical heater W 1250/2500 1250/2500 1250/2500 1250/2500
Liaisons hydrauliques
type Gas female threaded
2 pipes or 4 pipes "Cooling" pouce G ½" G ½" G ¾" G ¾"
4 pipes "Heating" pouce G ½" G ½" G ½" G ½"
Dimensions
VN / HN (LxPxH) mm 1122 x 220 x 430 1307 x 220 x 430 1121 x 220 x 530 1316 x 220 x 530
VC / HC (LxPxH) mm 1321 x 225 x 477 1506 x 225 x 477 1319 x 225 x 575 1506 x 225 x 575
Weight
VC / HC
2 pipes kg 30 35 35 47
4 pipes kg 32 37 37 49
VN / HN
2 pipes kg 22 26 27 38
4 pipes kg 24 28 29 40