IRC – Installation Operation Manual (IOM IRC 01 N 2ALL)

NTC - IR2
GB - 4
General information
The remote control works only with hydronic units.
For installation instructions of this unit, refer to the relevant
manuals.
The operating setting to the unit are sent by the remote control
through an infrared ray.
The emitter is placed on top of the remote control just over the
display (H).
For this reason, the remote control must be directed towards the
unit before sending any message and care must be taken that no
obstructions are between the remote control and the unit.
A small black arrow on the display left side indicates that the
message has been correctly sent.
An acoustical sound (beep) indicates that the message has been
correctly received by the unit.
For trouble-free installation, which should be carried out by a
Wall-mounted bracket
qualified installer.
Follow all current national safety code requirements.
After installation thoroughly test the system operation and
explain all system functions to the owner.
Leave this manual with the owner for consultation during
future periodic maintenance.
Dispose of packaging material in accordance with local
requirements.
The manufacturer denies any responsibility and warranty
shall be void if these installation instructions are not
observed.
Inspect equipment for damage due to improper transportation
or handling: file an immediate claim with the shipping
company. Do not install or use damaged units.
In case of any malfunctioning turn the unit off, disconnect the
mains power supply and contact a qualified service engineer.
M
V
V
25 mm
0,984 in
5 mm
0,196 in
IRC
GB
GB - 5
NTC - IR2
ENGLISH
Configuration menu
Refer to the figure at page 3 (Aspect and display).
With the remote control OFF press button B for at least 5 seconds
to access to the configuration menu. “1-” is displayed: this is the
first settable item of the menu. To check this items value press
button B again. The default value is displayed first.
To change this value, press button F or D. Press B to save the new
setting. To display and/or change another item (“2-”) press button B
and repeat the steps above.
If no button is pressed within 60 seconds, the system quits the
menu automatically. No message is sent.
The configuration menu is described in the following table:
1-
2-
3-
Item Value Description Displayed
Temperature units
C: Degrees C
F: Degrees F
System
Co
St
Set - point displaying
Ye
No
˚C -indicates that all temperatures will be displayed in
degrees C.
˚F -indicates that all temperatures will be displayed in
degrees F.
[Defaults: "C": Degrees ˚C]
Temp SP is shown thru bar graph
Temp SP is shown thru the 7 segments digits and .5 icon
[Defaults: "Co": Communicating]
The set-point value will be displayed on the IR2 lcd
The set-point value will be NOT displayed on the IR2 lcd
[Defaults: "Ye"]
NO
NO
YES
If "System" is Co, the
set - point will be not
displayed automatically.
4-
5-
6-
7-
8-
Set-point value
15,16,17,18,19,20,21,
22,23,24,25,26,27,28,
29,30,31,32 ˚C
59,60,61,62,63,64,65,
66,67,68,69,70,71,72,
73,74,75,76,77,78,79,
80,81,82,83,84,85,86,
87,88,89,90 ˚F
Reset step value
0;0,5;1;1,5;2 ˚C
0;1;2;3;4 ˚F
Fan speed type
F
U
Blind groups available
0
1
4
5
Blind Inclination
No
Ye
[Defaults: 22 ˚C; 72 ˚F]
[Default: "0,5" ˚C; "1" ˚F]
Fixed speed
Variable fan speed
[Default: "F" 3 fixed speeds]
There is no blind/groups to control: no icons will be
displayed
Just one blind group is available: “1” group icons will not
be illuminated
Four lights groups are available: “Lamp” and “4”
groups icons will be illuminated in the light menu
There is no group, but user can manage the blind
[Defaults: “0”: Blinds control disabled.]
The installed blinds doesn’t have the capability to
modify its inclination
The installed blinds has the motor able to change
its inclination.
[Default: “No” Blinds doesn’t have the capability to
change its inclination]
NO
YES
If the reset step value is
set to 0, the stand
alone mode is not
available. The IR remote
control and its display,
work as in
communicating mode
NO: In case of variable fan,
the icons available are
two: HIGH speed and
AUTO mode
YES: Once the blind menu
is selected, the groups icon
will be energized on the
lcd (no icons if just one
group is selected)
“A” and “1” icons are
energized in the blind
menu. User can manage
all blinds or just one
NO
The blind inclination
feature becomes active
into the Blind Menu. No
icon point out this feature
out of the blind menu
GB - 5
NTC - IR2
ENGLISH
Configuration menu
Refer to the figure at page 3 (Aspect and display).
With the remote control OFF press button B for at least 5 seconds
to access to the configuration menu. “1-” is displayed: this is the
first settable item of the menu. To check this items value press
button B again. The default value is displayed first.
To change this value, press button F or D. Press B to save the new
setting. To display and/or change another item (“2-”) press button B
and repeat the steps above.
If no button is pressed within 60 seconds, the system quits the
menu automatically. No message is sent.
The configuration menu is described in the following table:
1-
2-
3-
Item Value Description Displayed
Temperature units
C: Degrees C
F: Degrees F
System
Co
St
Set - point displaying
Ye
No
˚C -indicates that all temperatures will be displayed in
degrees C.
˚F -indicates that all temperatures will be displayed in
degrees F.
[Defaults: "C": Degrees ˚C]
Temp SP is shown thru bar graph
Temp SP is shown thru the 7 segments digits and .5 icon
[Defaults: "Co": Communicating]
The set-point value will be displayed on the IR2 lcd
The set-point value will be NOT displayed on the IR2 lcd
[Defaults: "Ye"]
NO
NO
YES
If "System" is Co, the
set - point will be not
displayed automatically.
4-
5-
6-
7-
8-
Set-point value
15,16,17,18,19,20,21,
22,23,24,25,26,27,28,
29,30,31,32 ˚C
59,60,61,62,63,64,65,
66,67,68,69,70,71,72,
73,74,75,76,77,78,79,
80,81,82,83,84,85,86,
87,88,89,90 ˚F
Reset step value
0;0,5;1;1,5;2 ˚C
0;1;2;3;4 ˚F
Fan speed type
F
U
Blind groups available
0
1
4
5
Blind Inclination
No
Ye
[Defaults: 22 ˚C; 72 ˚F]
[Default: "0,5" ˚C; "1" ˚F]
Fixed speed
Variable fan speed
[Default: "F" 3 fixed speeds]
There is no blind/groups to control: no icons will be
displayed
Just one blind group is available: “1” group icons will not
be illuminated
Four lights groups are available: “Lamp” and “4”
groups icons will be illuminated in the light menu
There is no group, but user can manage the blind
[Defaults: “0”: Blinds control disabled.]
The installed blinds doesn’t have the capability to
modify its inclination
The installed blinds has the motor able to change
its inclination.
[Default: “No” Blinds doesn’t have the capability to
change its inclination]
NO
YES
If the reset step value is
set to 0, the stand
alone mode is not
available. The IR remote
control and its display,
work as in
communicating mode
NO: In case of variable fan,
the icons available are
two: HIGH speed and
AUTO mode
YES: Once the blind menu
is selected, the groups icon
will be energized on the
lcd (no icons if just one
group is selected)
“A” and “1” icons are
energized in the blind
menu. User can manage
all blinds or just one
NO
The blind inclination
feature becomes active
into the Blind Menu. No
icon point out this feature
out of the blind menu
GB - 5
NTC - IR2
ENGLISH
Configuration menu
Refer to the figure at page 3 (Aspect and display).
With the remote control OFF press button B for at least 5 seconds
to access to the configuration menu. “1-” is displayed: this is the
first settable item of the menu. To check this items value press
button B again. The default value is displayed first.
To change this value, press button F or D. Press B to save the new
setting. To display and/or change another item (“2-”) press button B
and repeat the steps above.
If no button is pressed within 60 seconds, the system quits the
menu automatically. No message is sent.
The configuration menu is described in the following table:
1-
2-
3-
Item Value Description Displayed
Temperature units
C: Degrees C
F: Degrees F
System
Co
St
Set - point displaying
Ye
No
˚C -indicates that all temperatures will be displayed in
degrees C.
˚F -indicates that all temperatures will be displayed in
degrees F.
[Defaults: "C": Degrees ˚C]
Temp SP is shown thru bar graph
Temp SP is shown thru the 7 segments digits and .5 icon
[Defaults: "Co": Communicating]
The set-point value will be displayed on the IR2 lcd
The set-point value will be NOT displayed on the IR2 lcd
[Defaults: "Ye"]
NO
NO
YES
If "System" is Co, the
set - point will be not
displayed automatically.
4-
5-
6-
7-
8-
Set-point value
15,16,17,18,19,20,21,
22,23,24,25,26,27,28,
29,30,31,32 ˚C
59,60,61,62,63,64,65,
66,67,68,69,70,71,72,
73,74,75,76,77,78,79,
80,81,82,83,84,85,86,
87,88,89,90 ˚F
Reset step value
0;0,5;1;1,5;2 ˚C
0;1;2;3;4 ˚F
Fan speed type
F
U
Blind groups available
0
1
4
5
Blind Inclination
No
Ye
[Defaults: 22 ˚C; 72 ˚F]
[Default: "0,5" ˚C; "1" ˚F]
Fixed speed
Variable fan speed
[Default: "F" 3 fixed speeds]
There is no blind/groups to control: no icons will be
displayed
Just one blind group is available: “1” group icons will not
be illuminated
Four lights groups are available: “Lamp” and “4”
groups icons will be illuminated in the light menu
There is no group, but user can manage the blind
[Defaults: “0”: Blinds control disabled.]
The installed blinds doesn’t have the capability to
modify its inclination
The installed blinds has the motor able to change
its inclination.
[Default: “No” Blinds doesn’t have the capability to
change its inclination]
NO
YES
If the reset step value is
set to 0, the stand
alone mode is not
available. The IR remote
control and its display,
work as in
communicating mode
NO: In case of variable fan,
the icons available are
two: HIGH speed and
AUTO mode
YES: Once the blind menu
is selected, the groups icon
will be energized on the
lcd (no icons if just one
group is selected)
“A” and “1” icons are
energized in the blind
menu. User can manage
all blinds or just one
NO
The blind inclination
feature becomes active
into the Blind Menu. No
icon point out this feature
out of the blind menu
IRC
GB
IRC
IRC
E