IOM SYSAQUA 45 125 (IOM AQA 05 N 3GB)
Table Of Contents
- CONTENTS
- 1. GENERAL RECOMMENDATIONS
- 2. INSPECTION AND STORAGE
- 3. WARRANTY
- 4. PRESENTATION
- 5. CONTENTS OF PACKAGE
- 6. DIMENSIONS
- 7. HANDLING
- 8. TECHNICAL SPECIFICATIONS
- 9. INSTALLATION
- 10. HYDRAULIC LINKS
- 11. WIRING DIAGRAM AND LEGEND
- 12. ELECTRICAL CONNECTIONS
- 13. REGULATION
- 13.1. ORDER OF PRIORITY FOR CONTROL SYSTEMS
- 13.2. USER INTERFACE
- 13.3. INITIAL SETTINGS
- 13.4. LAUNCHING THE SYSAQUA SYSTEM
- 13.4.1. CONFIGURING INPUT D1
- 13.4.2. CONFIGURING INPUT D2
- 13.4.3. HEAT/COOL SELECTION
- 13.4.4. SELECTING THE OPERATING MODE
- 13.4.5. USER TEMPERATURE SETPOINTS AND ACTUAL SETPOINTS
- 13.4.6. WATER LAW
- 13.4.7. "VARIABLE PRIMARY FLOW” OPTION
- 13.4.8. ELECTRIC HEATING OPTION
- 13.4.9. REDUCED MODE
- 13.4.10. LIMITED CAPACITY
- 13.5. ALARMS
- 13.6. SCHEDULE
- 14. COMMISSIONING
- 15. IN CASE OF WARRANTY - MATERIAL RETURN PROCEDURE
- 16. ORDERING SERVICE AND SPARE PARTS ORDER
- 17. MAINTENANCE
- 18. TROUBLE SHOOTING
- DIMENSIONS
- REFRIGERANT CIRCUIT DIAGRAM
- HYDRAULIC CIRCUIT DIAGRAM
- PRESSURE LOSSES OF THE PLATE HEAT EXCHANGER
- HYDRAULIC PUMPS CURVES
- WIRING DIAGRAM
- DIMENSIONS
- SCHEMA DU CIRCUIT FRIGORIFIQUE
- SCHEMA DU CIRCUIT HYDRAULIQUE
- PERTE DE CHARGE DE L'ECHANGEUR A PLAQUES
- COURBES DES POMPES HYDRAULIQUES
- SCHEMAS ELECTRIQUES
- ABMESSUNGEN
- KÄLTEKREISLAUFDIAGRAMM
- HYDRAULISCHER SCHALTPLAN
- DRUCKVERLUST PLATTENWÄRMETAUSCHER
- KURVEN VON HYDRAULIKPUMPEN
- STROMLAUFPLANS
- DIMENSIONI
- SCHEMA DEL CIRCUITO REFRIGERANTE
- SCHEMA CIRCUITALE IDRAULICO
- PERDITA DI CARICO SCAMBIATORE A PIASTRE
- CURVE DELLE POMPE IDRAULICHE
- SCHEMA ELETRICO
- DIMENSIONES
- ESQUEMA DEL CIRCUITO FRIGORIFÍCO
- ESQUEMA CIRCULAR HIDRÁULICO
- PÉRDIDA DE CARGA INTERCAMBIADOR DE PLACAS
- CURVAS BOMBAS HIDRÁULICAS
- ESQUEMA ELECTRICO
English
The mains hydraulic circuit will provide a constant water ow on the refrigerating uid/water plate
exchanger and in case of load variation.
Caution
When choosing and installing water pipes, you must consult and observe all current local standards,
regulations and instructions.
Caution
The expansion tank must be dimensioned to be able to absorb an expansion corresponding to 2%
total volume of water contained in the installation (exchanger, piping, installations and buffer tank,
if present).
Caution
THE WARRANTY DOES NOT COVER DAMAGE DUE TO CORROSION RESULTING FROM ELECTROLYTIC
PHENOMENA.
Caution
To avoid any risk of foreign bodies entering the appliance and to guarantee operating performance,
IT IS IMPERATIVE TO INSTALL WATER FILTER on the SYSAQUA inlet pipe.
Caution
THE MANUFACTURER'S WARRANTY IS VOID IF THE FILTER SUPPLIED WITH
THE SYSAQUA IS NOT INSTALLED TO PROTECT THE APPLIANCE
Caution
13SYSAQUA
10. HYDRAULIC LINKS
10.1. MAIN HYDRAULIC CIRCUIT
You must design the pipe network with the minimum number of bends and keep the number of changes in
height to the strict minimum. This will reduce installation costs and ensure optimum system performance.
The pipe network must include:
² A vibration elimination system (e.g.: link hoses) on all pipes connected to the appliance in order to
reduce vibrations and noise transmitted to the building fabric.
² A balancing valve on the water outlet pipe in order to adjust the water ow.
² Stop cocks to isolate the hydraulic circuit during maintenance.
² Manual or automatic bleed valves at the highest point on the water circuit.
² Draining connectors at all low points to allow complete circuit draining.
² A circulation pump guaranteeing ow necessary for the operation of the SYSAQUA unit.
² A diaphragm expansion tank tted with a safety and draining valve must be visible.
² A low water pressure sensor to secure the water pump against cavitation if the water pressure in the
circuit decreases.
² The installation of thermometers and pressure gauges on the heat exchanger inlet and outlet to
facilitate day-to-day controls and system maintenance.
² An element ensuring ground continuity of all piping. An unbalance of grounding connection points
can cause corrosion electrolytic.
10.2. ANTI-CLOGGING PROTECTION
Failing that, SYSAQUA's heat plate exchanger would clog up soon after being commissioned. Proper
operation of the SYSAQUA would be disturbed
by a reduced water ow or the partial
blockage of certain heat plates. The heat plate
exchanger could be IRREVERSIBLY damaged
if the water ow were not sufciently high.
A link smaller than or equal to 800µm is
recommended