IOM SYSAQUA 45 125 (IOM AQA 05 N 3GB)

Table Of Contents
English
43SYSAQUA
TASKS PER COMPONENTS ACTIONS
1
month
3
month
s
6
months
12
months
24
months
Recommended inspection and maintenance
interval
3.10 Check filter cleanliness. Clean
3.11
Check that the hydraulic circuit is filled
properly
3.12
Check the condition of the expansion
tank (presence of excess corrosion, or gas
pressure loss)
Replace if required.
3.13 Check the water pump
If the unit has not been used for a
long time, manually rotate the pump
shaft and check that it turns freely.
For a unit equipped with a double
pump, it is recommended to switch
from one pump to the other every
month or to check that the pump
shaft turns freely to prevent the
liners sticking.
Change the pump liner after 15,000
hours running with anti-freeze or
25,000 hours running with water.
3.14
Verify that low water pressure sensor works
perfectly
3.15
Record the water temperatures at the plate
exchanger inlet and outlet.
4 - ELECTRIC CIRCUIT
4.1
Check the electrical voltage applied to the
unit, which must remain stable within the
tolerances specified in the information
plates.
4.2
Check that the main supply cable is void of
alterations likely to impact the insulation.
Replace if required.
4.3
Check the grounding of the metallic
structure
Repair if required.
4.4 Inspect the contacts. Replace if required.
4.5
Check that all electrical connections of the
device are tight
Tighten if required.
4.6
Check the thermal protection relays of the
motors
Replace if required.
4.7
Check the nominal intensity and condition
of the fuses.
4.8 Check the condition of the condensers.
4.9
Clean the compressed air electrical unit to
remove any dust or other contaminants
building up.
4.10 Check the motor windings are insulated.
5 - FAN(S)
5.1
Check the lack of contamination, corrosion
or damage.
Clean if required
5.2 Check proper fastening of the fan. Tighten if required.
5.3 Check the vanes to guarantee balancing. Clean if required.
5.4 Check the bearings for noise. Repair if required.
5.5
Check the condition of the grease and
greasers (unless if permanently lubricated).
Re-grease if required (Lithium soap
grease DIN 51825-K3N for fans type
K, K1, K2).
T>70 °C
5.6 Check the condition of the fan motor.
6 - REGULATION
6.1 Check the condition of the alarms
Acknowledge them after taking
them into consideration
6.2 Check the setting points
6.3 Check the operation of all probes