Scroll Compressor Refrigerant R410A SYSAQUA Air Cooled Water Chillers SYSAQUA.L (Cooling Only) / SYSAQUA.H (Heat Pump) Models 140 to 210 143.7 to 217.6kW 125.4 to 208.
SYSAQUA Key Points Energy class SCOP A+, Phase sequence monitor supplied as standard, R410A refrigerant, User-friendly controller that allows to reduce the need of an external water tank in most of comfort air conditioning installations, Units are optimized for partial load operation, High ESEER and SCOP, 2 refrigerant circuits each equipped with 2 compressors fitted in tandem.
2 SYSAQUA Specifications General The new SYSAQUA.L/SYSAQUA.H 140 to 210 have been designed and optimized to operate with R410A refrigerant fluid. They are of dual refrigerant circuit type. They are available in cooling only (SYSAQUA.L) and heat pump (SYSAQUA.H) versions. Each versions consists of 5 sizes (140, 150, 170, 190 and 210) and covers a nominal cooling capacity range from 125 to 208 kW and a nominal heating capacity range from 143 to 217 kW.
SYSAQUA Specifications Control panel Water flow switch. The units are fitted with an external control panel that displays the operating parameters and alarms. Water filter (supplied loose). High pressure switch. The control panel is accessible from exterior without removing any parts, nor shutting down the unit, because it is placed on an external panel. High and low pressure transducers. Evaporator antifreeze electric heater. Crankcase heater. The SYSAQUA.L/SYSAQUA.
4 SYSAQUA Models designation SYSAQUA140 . H . 1P-SP . TTS . SYS . HPF . 1 2 3 4 5 6 REP. 7 . + . CG .
SYSAQUA Refrigerant Flow Diagram Cooling only version - SYSAQUA140.L to SYSAQUA150.L HP1 FPC1 CDT1 CDT2 OFA OFB FPC2 HP2 OFC OFD OAT M2-1 M2-2 M1-1 M1-2 3-1 CST1 OCT1 4-1 FPE1 WATER FPE2 8 6-1 5-1 3-2 CST2 6-2 5-2 4-2 OCT2 Cooling only version - SYSAQUA170.L HP1 FPC1 CDT1 CDT2 OFA OFB FPC2 HP2 OFC OFD OAT M2-1 M2-2 M1-1 M1-2 3-1 CST1 OCT1 4-1 FPE1 WATER FPE2 8 6-1 5-1 3-2 CST2 6-2 5-2 4-2 OCT2 Cooling only version - SYSAQUA190.L to SYSAQUA210.
6 SYSAQUA Refrigerant Flow Diagram Heat pump version - SYSAQUA140.H to SYSAQUA150.H HP1 FPC1 CDT1 CDT2 RV1 OFA OFB CST1 OCT1 HP2 RV2 OAT 4-1 FPE1 WATER 6-1 5-1 OFC OFD M2-1 M2-2 M1-1 M1-2 3-1 FPC2 FPE2 3-2 CST2 8 7-1 7-2 6-2 5-2 4-2 OCT2 CoHeat pump version - SYSAQUA170.
SYSAQUA Hydraulic Circuit Diagram Without pump version PA FT EWT CL EWC PHE RAG RAG FS CL LWC VD LWT Recommended installation - Single pump version VE MN VR CF VA WPS FT WP PA SS PHE PA RAG RAG MN CF EWT CL EWC WT WPT VA FS CL LWC VD VD LWT VV Recommended installation - Double pump version VE MN VR CF WP VA PA WPS FT SS WP VA WPT EWT PHE PA MN CF CL EWC WT FS LWC VD VD RAG RAG CL LWT VV Installation recommandée Globe valve (option) VA Drain valv
8 SYSAQUA Energy performance Energy class More efficient A++ A+ A B C D E F G Less efficient SYSAQUA SYSAQUA140.H SYSAQUA150.H SYSAQUA170.H SYSAQUA190.H SYSAQUA210.H SCOP 3.32 A++ 3.36 A++ 3.31 A++ 3.29 A++ 3.23 A++ Class + A A B C D E F G + A A B C D E F G + A A B C D E F G + A A B C D E F G A+ A B C D E F G Seasonal space heating energy efficiency class according to the Delegated Regulation No. 811/2013 of the European Commission.
SYSAQUA Operating Limits SYSAQUA.L/SYSAQUA.H in cooling mode 55 50 45 Air temperature (°C) 40 35 BRINES or WATER + GLYCOL 30 WATER 25 20 15 10 5 BRINES or WATER + GLYCOL + Fan speed controller 0 -5 WATER + Fan speed controller -10 -15 -15 -10 -5 0 5 10 Leaving water temperature (°C) 15 20 SYSAQUA.
10 SYSAQUA Correction Factors Fouling factors - Evaporator Fouling factor (m2.°C/kW) Capacity Power input 0.044 1.000 1.000 0.088 0.987 0.995 0.176 0.964 0.985 0.352 0.915 0.962 Fouling factor (m2.°C/kW) Capacity Power input 0.044 1.000 1.000 0.088 0.987 1.023 0.176 0.955 1.068 0.352 0.910 1.135 Altitude (m) Capacity Power input 0 1.000 1.000 600 0.987 1.010 1 200 0.973 1.020 1 800 0.958 1.030 2 400 0.943 1.
SYSAQUA Physical Data - SYSAQUA.L SYSAQUA - Cooling only version Cooling capacity Power input Total EER 100% (1) Energy class EER (2) SEER (2) hsc (2) Energy class SEER Power supply Startup type Maximum operating current Startup current (WITHOUT Soft Starter) Startup current (WITH Soft Starter) REFRIGERANT Type Number of refrigerant circuit Charge (3) COMPRESSORS kW kW SYSAQUA140.L SYSAQUA150.L SYSAQUA170.L SYSAQUA190.L SYSAQUA210.L A A A 134.0 147.0 44.2 49.0 3.03 3.00 B B 4.35 4.
12 SYSAQUA Physical Data - SYSAQUA.H SYSAQUA - Heat pump version Cooling capacity Power input Total EER 100% (1) Energy class EER (2) SEER (2) hsc (2) Energy class SEER Heating capacity Power input Total COP 100% (1) Energy class COP (2) SCOP hsh (2) Energy class SCOP (2) Power supply Startup type Maximum operating current Startup current (WITHOUT Soft Starter) Startup current (WITH Soft Starter) REFRIGERANT Type Number of refrigerant circuit Charge (3) COMPRESSORSS Number Type A A A SYSAQUA140.
SYSAQUA Weight Sizes SYSAQUA.L - without pump SYSAQUA.
14 SYSAQUA Acoustical Data Sound power level Lw-dB - Without pump S Y S A Q U A . L / Frequency in octave band (Hz) SYSAQUA.H 125 250 500 models 4000 Lw global dB(A) Sound pressure level dB(A) * 1000 2000 SYSAQUA140 77 79 82 81 79 74 85.4 53.4 SYSAQUA150 77 79 82 81 79 74 85.4 53.4 SYSAQUA170 79 81 83 82 81 76 87.0 55.0 SYSAQUA190 81 82 83 83 83 77 88.1 56.1 SYSAQUA210 81 82 83 83 83 77 88.1 56.
SYSAQUA Water Pressure Drop of Indoor Heat Exchanger 1000 900 800 700 600 500 400 300 SYSAQUA 140-150 100 90 80 70 60 50 40 SYSAQUA 170-190-210 30 20 10 9 2 190 240 3 170 8 7 6 5 4 140 150 Pressure loss (kPa) 200 1 1 2 3 4 5 6 7 8 9 10 20 Water flow (m /h) 3 30 40 50 60 70 80 90 100 15
SYSAQUA Water Pump Curves SYSAQUA 140 - 150 - 170 - Standard pump 200 50 Hz Available pressure (kPa) 180 160 45 Hz 140 120 40 Hz 100 80 35 Hz 60 30 Hz 40 20 0 0 5 10 15 20 25 Water flow (m3/h) 30 35 40 3 2.5 Power Input (kW) 16 2 50 Hz 1.5 45 Hz 40 Hz 1 35 Hz 30 Hz 0.
SYSAQUA Water Pump Curves SYSAQUA 190 - 210 - Standard pump 200 Available pressure (kPa) 180 160 50 Hz 140 45 Hz 120 100 40 Hz 80 35 Hz 60 30 Hz 40 20 0 0 5 10 15 20 25 Water flow (m3/h) 30 35 40 20 25 Water flow (m3/h) 30 35 40 3.5 Power Input (kW) 3 2.5 50 Hz 2 45 Hz 1.5 40 Hz 1 35 Hz 30 Hz 0.
SYSAQUA Water Pump Curves SYSAQUA 140 - 150 - 170 - 190 - High pressure pump 350 50 Hz Available pressure (kPa) 300 250 45 Hz 200 40 Hz 150 35 Hz 100 30 Hz 50 0 0 5 10 15 20 25 Water flow (m3/h) 30 35 40 20 25 Water flow (m3/h) 30 35 40 5 4.5 4 Power Input (kW) 18 3.5 50 Hz 3 2.5 45 Hz 2 40 Hz 1.5 35 Hz 30 Hz 1 0.
SYSAQUA Water Pump Curves SYSAQUA 210 - High pressure pump 400 50 Hz Available pressure (kPa) 350 300 45 Hz 250 40 Hz 200 150 35 Hz 100 30 Hz 50 0 0 5 10 15 20 25 Water flow (m3/h) 30 35 40 20 25 Water flow (m3/h) 30 35 40 6 Power Input (kW) 5 4 50 Hz 3 45 Hz 40 Hz 2 35 Hz 30 Hz 1 0 0 5 10 15 19
SYSAQUA Dimensions (mm) SYSAQUA WITHOUT PUMP 1249 1145 Ø17 2148 152 1249 1145 559 171 2321 (SYSAQUA 170-190-210) 2295 (SYSAQUA 140-150) 152 2804 Ø2"1/2 1100 48 2210 20 INTLET 2856 WATER OUTLET
SYSAQUA Dimensions (mm) SYSAQUA WITH 1 PUMP 1249 1145 Ø17 2148 152 1249 1145 2804 171 236 2321 (SYSAQUA 170-190-210) 2295 (SYSAQUA 140-150) 152 700 1100 2210 48 INTLET 2856 WATER OUTLET Ø2"1/2 21
SYSAQUA Dimensions (mm) SYSAQUA WITH 2 PUMPS 1249 1145 Ø17 2148 152 1249 1145 171 236 2321 (SYSAQUA 170-190-210) 2295 (SYSAQUA 140-150) 152 700 2804 1100 48 2210 22 INTLET 2856 WATER OUTLET Ø2"1/2
SYSAQUA Dimensions (mm) SYSAQUA WITH 1 PUMP AND BUFFER TANK 1249 1145 Ø17 2148 152 1249 1145 480 236 2321 (SYSAQUA 170-190-210) 2295 (SYSAQUA 140-150) 152 2804 700 Ø2"1/2 1740 48 2210 864 3666 INTLET OUTLET WATER 23
SYSAQUA Dimensions (mm) SYSAQUA WITH 2 PUMPS AND BUFFER TANK 1249 1145 Ø17 2148 152 1249 1145 480 236 2321 (SYSAQUA 170-190-210) 2295 (SYSAQUA 140-150) 152 2804 700 Ø2"1/2 1740 864 48 2210 24 3666 INTLET OUTLET WATER
SYSAQUA Space Requirements (mm) SYSAQUA WITHOUT BUFFER TANK 5 000 1 500 1 500 1 500 1 500 SYSAQUA WITH BUFFER TANK 5 000 2 000 1 500 1 500 1 500 25
SYSAQUA Masses distributions SYSAQUA.L 152 1249 1145 P4 P5 P6 2148 26 P3 P2 152 1249 P1 1145 Rubber pads Spring damper M P1 P2 P3 P4 P5 P6 kg kg M P1 P2 P3 P4 P5 P6 kg kg kg kg kg kg kg kg kg kg kg kg 1 440 270 250 220 210 230 260 SYSAQUA140.H.HB 1 440 270 250 230 210 230 250 SYSAQUA140.L.1P-SP 1 530 280 270 260 230 240 250 SYSAQUA140.H.1P-SP 1 530 280 270 260 230 240 250 SYSAQUA140.L.1P-HP 1 560 280 280 270 240 240 250 SYSAQUA140.
SYSAQUA Masses distributions SYSAQUA.H 152 1249 1145 P5 P6 2148 P4 P3 P2 152 1249 P1 1145 Rubber pads Spring damper M P1 P2 P3 P4 P5 P6 kg kg M P1 P2 P3 P4 P5 P6 kg kg kg kg kg kg kg kg kg kg kg kg 1 590 300 270 250 230 260 280 SYSAQUA140.H.HB 1 590 300 280 250 230 260 280 SYSAQUA140.L.1P-SP 1 680 310 300 290 260 270 280 SYSAQUA140.H.1P-SP 1 680 300 300 290 260 260 270 SYSAQUA140.L.1P-HP 1 720 310 300 300 270 270 270 SYSAQUA140.H.
SYSAQUA Masses distributions SYSAQUA.L with buffer tank 152 1249 1145 P4 P5 P6 2148 28 P3 P2 152 P1 1249 1145 Rubber pads Spring damper M P1 P2 P3 P4 P5 P6 kg kg M P1 P2 P3 P4 P5 P6 kg kg kg kg kg kg kg kg kg kg kg kg 1 880 170 280 390 460 350 230 SYSAQUA140.H.HB 1 880 220 220 410 490 270 270 SYSAQUA140.L.1P-SP 1 970 170 300 430 480 360 230 SYSAQUA140.H.1P-SP 1 970 230 240 450 510 270 260 SYSAQUA140.L.
SYSAQUA Masses distributions SYSAQUA.H with buffer tank 152 1249 1145 P5 P6 2148 P4 P3 P2 152 P1 1249 1145 Rubber pads Spring damper M P1 P2 P3 P4 P5 P6 kg kg M P1 P2 P3 P4 P5 P6 kg kg kg kg kg kg kg kg kg kg kg kg 2 030 190 300 420 480 370 260 SYSAQUA140.H.HB 2 030 240 240 440 530 290 290 SYSAQUA140.L.1P-SP 2 120 200 330 460 510 380 250 SYSAQUA140.H.1P-SP 2 120 250 260 490 550 290 290 SYSAQUA140.L.
30 SYSAQUA Notes
Systemair AC SAS · route de Verneuil, 27570 Tillières-sur- Avre · Tél. 02 32 60 61 00 · Fax 02 32 32 55 13 Systemair · EDM AQA2-S-7GB/08.20 - Supersedes : EDM AQA2-S-6GB/04.19 As part of our ongoing product improvement programme, our products are subject to change without prior notice. Non contractual photos. www.systemair.