SYSTEMP – Installation Operation Manual (IOM SYSTEMP rev.N)

Table Of Contents
31
5 ADJUSTABLE AND VENTILATED PLINTHS (ACCESSORY)
When installing plinths it is advisable to place a layer of vibration damping material (rubber or equivalent material with a
minimum thickness of 10 mm) between them and the oor to avoid transmitting vibrations to the structure of the building.
The interposition of vibration damping material also enables the recovery of a slight lack of atness of the oor and to con-
tain the noise level of installation.
It is also advisable to place a seal (rubber or equivalent material with minimum 5 mm thickness) between them and the unit
so as to guarantee the air-tightness of the element.
Below are the various types of plenums and plinths:
Adjustable and ventilated plinths
Type Front View Right/Left side view
Adjustable plinths
Ventilated plinths (G Series)
5.1 PLINTH DIMENSIONS
The dimensions of the plinths are found in the order conrmation or in the following tables for standard models (identied
by the code number sequence).
Adjustable and ventilated plinth dimensions
Standard models
Plan dimensions - Standard model dimensions (mm)
Length Depth Minimum/Maximum height
P Series
071 – 141 – 10 – 20 750 580
300/600
211 – 251 – 30 – 50 860
850
301 – 321 – 322 – 60 – 70 1410
361 – 461 – 422 – 512 – 80 – 110 1750
662 – 852 2300
932 – 160 2640
932 TS 3190
220 3495
G Series
70 1320
900
550 (set height)
1000 (set height)
461 - 612 1490
150
1840
150 XH 1020
932 2390
900
230
2740
230 XH 1020
1342 3120
900
300 4020