AQUASCOP HT Engineering Data Manual (EDM PACHT S 3GB)

Aqu@Scop HT V2 / Aqu@Scop HT Split
21
Performance Data
Aqu@Scop HT V2
Aqu@Scop HT V2 models 12-6 14-7 18-9
Outdoor air condition
+7 °C / +6 °C WB
Water condition 30/35 °C
Heating capacity single-compressor kW 6.43 8.51 9.90
Power input kW 1.53 1.92 2.15
COP 4.20 4.43 4.61
Water condition 45 °C
Heating capacity single-compressor kW 5.86 7.93 9.46
Power input kW 1.86 2.35 2.67
COP 3.15 3.37 3.54
Water condition 55 °C
Heating capacity dual-compressor kW 5.36 7.22 8.75
Power input kW 2.30 2.85 3.27
COP with defrost 2.33 2.53 2.68
Outdoor air condition
+2 °C / +1 °C WB
Water condition 35 °C
Heating capacity dual-compressor kW 10.52 13.26 15.63
Power input kW 2.99 3.82 4.39
COP with defrost 3.52 3.47 3.56
Outdoor air condition
-7 °C / -8 °C WB
Water condition 35 °C
Heating capacity dual-compressor kW 8.21 10.89 12.46
Power input kW 2.78 3.59 4.05
COP with defrost 2.95 3.03 3.08
Water condition 55 °C
Heating capacity dual-compressor kW 8.57 10.92 12.69
Power input kW 3.74 4.63 5.29
COP with defrost 2.29 2.36 2.40
Water condition 65 °C
Heating capacity dual-compressor kW 8.49 10.90 12.25
Power input kW 4.45 5.30 5.92
COP with defrost 1.91 2.06 2.07
Outdoor air condition
-15 °C
Water condition 35 °C
Heating capacity dual-compressor kW 7.95 10.44 11.94
Power input kW 2.78 3.58 4.04
COP with defrost 2.86 2.92 2.96
Outdoor air condition
-20 °C
Water condition 55 °C
Heating capacity dual-compressor kW 8.03 10.32 11.28
Power input kW 3.95 4.73 5.22
COP with defrost 2.03 2.18 2.16
Aqu@Scop HT V2 models 12-6 14-7 18-9
Nominal water flow m
3
/h 1030 1370 1580
Available hydraulic pressure - High speed kPa 55 48 55
Operating limits (outdoor temperature) °C -20
Outlet water temperature Min. / Max. °C +25/+65
WB : Wet bulb.