AQUASCOP HT Engineering Data Manual (EDM PACHT S 3GB)

L = 45 meters max.
L = 45 meters max.
H = 15 meters max.
L = 45 meters max.
H = 15 meters max.
Aqu@Scop HT V2 / Aqu@Scop HT Split
8
Length
(meter)
Ø gas line
(inch)
Ø liquid
line
(inch)
Additional
charge
(gramme)
20 5/8" 3/8" 0
21 5/8" 3/8" 57
22 5/8" 3/8" 114
23 5/8" 3/8" 171
24 5/8" 3/8" 228
25 5/8" 3/8" 285
26 3/4" 1/2" 1792
27 3/4" 1/2" 1904
28 3/4" 1/2" 2016
29 3/4" 1/2" 2128
30 3/4" 1/2" 2240
31 3/4" 1/2" 2352
32 3/4" 1/2" 2464
33 3/4" 1/2" 2576
34 3/4" 1/2" 2688
35 3/4" 1/2" 2800
36 3/4" 1/2" 2912
37 3/4" 1/2" 3024
38 3/4" 1/2" 3136
39 3/4" 1/2" 3248
40 3/4" 1/2" 3360
41 3/4" 1/2" 3472
42 3/4" 1/2" 3584
43 3/4" 1/2" 3696
44 3/4" 1/2" 3808
45 3/4" 1/2" 3920
Refrigerant Pipings and Additional Charges
Aqu@Scop HT Split