IMO FRQ5S 4A 10A 16A V2
Table Of Contents
- 1 General notes
- 2 Safety instructions
- 2.1 Intended use
- 2.2 Explanations of symbols
- 2.3 Product safety
- 2.3 Product safety
- 2.4 Requirements placed on the personnel / due diligence
- 2.4 Requirements placed on the personnel / due diligence
- 2.5 Start–up and during operation
- 2.5 Start–up and during operation
- 2.6 Working on device / Hazards through
- 2.7 Modifications / interventions in the device
- 2.8 Operator’s obligation of diligence
- 2.9 Employment of external personnel
- 3 Product overview
- 4 Mounting
- 5 Electrical installation
- 5.1 Safety precautions
- 5.2 EMC–compatible installation
- 5.3 Mains connection
- 5.4 Residual–current–operated protective device
- 5.5 Inverter output
- 5.6 Motor protection
- 5.7 Voltage supply for external devices (+, GND)
- 5.8 Enable, Device ON / OFF (Digital In 1 =D1)
- 5.9 Relay outputs
- 5.10 Bypass circuit
- 5.11 Potential at control voltage connections
- 6 Start–up
- 7 Diagnostics / Faults
- 8 Enclosure
8 Enclosure
8.1 Technical data
Type
FRQ5S-4A FRQ5S-10A FRQ5S-16A
Part-No.
36233
(308278-42)
36234
(308279-42)
37276
(308301-42)
Rated current output {1} 4 A 10 A 16 A
Rated current input {2}
(I fundamental component @ 50 Hz)
3.8 A
(3.5 A)
9.4 A
(8.6 A)
15.2 A
(14.0 A)
Recommended motor output {3} 1.5 kW 4.0 kW 7.5 kW
Max. line fuse {4} 10 A 16 A 20 A
Max. leakage current according to the
dened networks of DIN EN 60990 (de-
pending on connected line voltage *)
< 3.5 mA < 3.5 mA
< 3,5 mA @ < 480 V *
≥ 3,5 mA @ ≥ 480 V *
Max. heat dissipation approx. {2} 80 W 200 W 360 W
Rated temperature 55 °C 40 °C 40 °C
Weight 5.5 kg 6.4 kg 7.1 kg
{1} Rated current output
current indication rating plate @ rated voltage, @ rated temperature
(cos φ 0.8 at the output)
{2} At rated voltage (cos φ 0.8 at the output), values for different specifications on request.
{3} Example for power of a 4 pole motor. For the dimension of the frequency inverter size the rated
current of the motor is crucial!
{4} Max. supply side line fuse according to DIN EN 60204-1 classification VDE0113 chapter 1
Line voltage* 3 ~ 208...480 V (-15 bis +10 %), 50/60 Hz
Rated voltage 400 V
Maximal output voltage approx. 95 % from U
line
Maximal output frequency 50 Hz
Edgefrequency 48,5 Hz
U/f-characteristic curve square
Switching frequency 16 kHz
Rampup time 20 sec
Rampdown time 20 sec
Current limit FRQ5S-4A: 120 %, FRQ5S-10A: 110 %, FRQ5S-16A: 120 %
Power factor > 0.9
Voltage supply for external devi-
ces
+24 V ± 20 %, I
max
70 mA
Heat dissipation in standby op-
eration
approx. 3 W
Digital input “D1” Input resistance: R
i
approx. 4 kΩ
Voltage range high level: 10....30 V DC
Voltage range low level: 0....4 V DC
Operating Instructions FRQ5S-4/10/16A Enclosure