Operation instructions Danfoss ENG

Parameters
FC
+24 V
+24 V
D IN
D IN
D IN
COM
D IN
D IN
D IN
D IN
+10 V
A IN
A IN
COM
A OUT
COM
12
13
18
19
20
27
29
32
33
37
50
53
54
55
42
39
130BB803.10
Function Setting
5-10 Terminal
18 Digital
Input
[9] Latched
Start
5-12 Terminal
27 Digital
Input
[6] Stop
Inverse
* = Default Value
Notes/comments:
If 5-12 Terminal 27 Digital
Input is set to [0] No
operation, a jumper wire to
terminal 27 is not needed.
D IN 37 is an option.
Table 6.6 Pulse Start/Stop
Speed
130BB806.10
Latched Start (18)
Stop Inverse (27)
Figure 6.3 Latched Start/Stop Inverse
Parameters
FC
+24 V
+24 V
D IN
D IN
D IN
COM
D IN
D IN
D IN
D IN
+10 V
A IN
A IN
COM
A OUT
COM
12
13
18
19
20
27
29
32
33
37
50
53
54
55
42
39
130BB934.10
Function Setting
5-10 Terminal 18
Digital Input
[8] Start
5-11 Terminal 19
Digital Input
[10]
Reversing*
5-12 Terminal 27
Digital Input
[0] No
operation
5-14 Terminal 32
Digital Input
[16] Preset
ref bit 0
5-15 Terminal 33
Digital Input
[17] Preset
ref bit 1
3-10 Preset
Reference
Preset ref. 0
Preset ref. 1
Preset ref. 2
Preset ref. 3
25%
50%
75%
100%
* = Default Value
Notes/comments:
D IN 37 is an option.
Table 6.7 Start/Stop with Reversing and Four Preset Speeds
Application Set-up Examples Instruction Manual
32 Danfoss A/S © Rev. 11/06/2014 All rights reserved. MG11AK22
66