OPERATION INSTRUCTIONS DANFOSS ENG

Recommended max. fuse
Power (hp
[kW])
SIBA
Type RK1
Littlefuse
Type RK1
Ferraz-
Shawmut
Type CC
Ferraz-
Shawmut
Type RK1
3)
Bussmann
Type JFHR2
2)
Littelfuse
JFHR2
Ferraz-
Shawmut
JFHR2
4)
Ferraz-
Shawmut
J
1.5 [1.1] 5017906-010 KLN-R-10 ATM-R-10 A2K-10-R FWX-10 - - HSJ-10
2 [1.5] 5017906-016 KLN-R-15 ATM-R-15 A2K-15-R FWX-15 - - HSJ-15
3 [2.2] 5017906-020 KLN-R-20 ATM-R-20 A2K-20-R FWX-20 - - HSJ-20
4 [3.0] 5017906-025 KLN-R-25 ATM-R-25 A2K-25-R FWX-25 - - HSJ-25
5 [3.7] 5012406-032 KLN-R-30 ATM-R-30 A2K-30-R FWX-30 - - HSJ-30
7.5–10
[5.5–7.5]
5014006-050 KLN-R-50 - A2K-50-R FWX-50 - - HSJ-50
15 [11] 5014006-063 KLN-R-60 - A2K-60-R FWX-60 - - HSJ-60
20 [15] 5014006-080 KLN-R-80 - A2K-80-R FWX-80 - - HSJ-80
25–30
[18.5–22]
2028220-125 KLN-R-125 - A2K-125-R FWX-125 - - HSJ-125
40 [30] 2028220-150 KLN-R-150 - A2K-150-R FWX-150 L25S-150 A25X-150 HSJ-150
50 [37] 2028220-200 KLN-R-200 - A2K-200-R FWX-200 L25S-200 A25X-200 HSJ-200
60 [45] 2028220-250 KLN-R-250 - A2K-250-R FWX-250 L25S-250 A25X-250 HSJ-250
Table 8.18 3x200–240 V, Enclosure Types A, B and C
1) KTS fuses from Bussmann may substitute KTN for 240 V adjustable frequency drives.
2) FWH fuses from Bussmann may substitute FWX for 240 V adjustable frequency drives.
3) A6KR fuses from FERRAZ SHAWMUT may substitute A2KR for 240 V adjustable frequency drives.
4) A50X fuses from FERRAZ SHAWMUT may substitute A25X for 240 V adjustable frequency drives.
3x380–480 V
Recommended max. fuse
Power
(hp [kW])
Bussmann
Type RK1
Bussmann
Type J
Bussmann
Type T
Bussmann
Type CC
Bussmann
Type CC
Bussmann
Type CC
1.5 [1.1] KTS-R-6 JKS-6 JJS-6 FNQ-R-6 KTK-R-6 LP-CC-6
2–3
[1.5–2.2]
KTS-R-10 JKS-10 JJS-10 FNQ-R-10 KTK-R-10 LP-CC-10
4 [3] KTS-R-15 JKS-15 JJS-15 FNQ-R-15 KTK-R-15 LP-CC-15
5 [4] KTS-R-20 JKS-20 JJS-20 FNQ-R-20 KTK-R-20 LP-CC-20
7.5 [5.5] KTS-R-25 JKS-25 JJS-25 FNQ-R-25 KTK-R-25 LP-CC-25
10 [7.5] KTS-R-30 JKS-30 JJS-30 FNQ-R-30 KTK-R-30 LP-CC-30
15–20
[11–15]
KTS-R-40 JKS-40 JJS-40 - - -
24 [18] KTS-R-50 JKS-50 JJS-50 - - -
30 [22] KTS-R-60 JKS-60 JJS-60 - - -
40 [30] KTS-R-80 JKS-80 JJS-80 - - -
50 [37] KTS-R-100 JKS-100 JJS-100 - - -
60 [45] KTS-R-125 JKS-125 JJS-125 - - -
75 [55] KTS-R-150 JKS-150 JJS-150 - - -
100 [75] KTS-R-200 JKS-200 JJS-200 - - -
125 [90] KTS-R-250 JKS-250 JJS-250 - - -
Table 8.19 3x380–480 V, Enclosure Types A, B and C
Specifications Instruction Manual
68 Danfoss A/S © Rev. 11/06/2014 All rights reserved. MG11AK22