OPERATION INSTRUCTIONS DANFOSS ENG

Safe Torque Off Terminal 37
3), 4)
(Terminal 37 is fixed PNP logic)
Voltage level 0–24 V DC
Voltage level, logic'0' PNP <4 V DC
Voltage level, logic'1' PNP >20 V DC
Maximum voltage on input 28 V DC
Typical input current at 24 V 50 mA rms
Typical input current at 20 V 60 mA rms
Input capacitance 400 nF
All digital inputs are galvanically isolated from the supply voltage (PELV) and other high-voltage terminals.
1) Terminals 27 and 29 can also be programmed as output.
2) Except Safe Torque Off input Terminal 37.
3) See chapter 4.8 Control Wiring for further information about terminal 37 and Safe Torque Off.
4) When using a contactor with a DC coil inside in combination with Safe Torque Off, it is important to make a return way for
the current from the coil when turning it off. This can be done by using a freewheel diode (or, alternatively, a 30 or 50 V MOV for
quicker response time) across the coil. Typical contactors can be bought with this diode.
Analog inputs
Number of analog inputs 2
Terminal number 53, 54
Modes Voltage or current
Mode select Switch S201 and switch S202
Voltage mode Switch S201/switch S202 = OFF (U)
Voltage level -10 to +10 V (scalable)
Input resistance, R
i
approx. 10 kΩ
Max. voltage ±20 V
Current mode Switch S201/switch S202 = ON (I)
Current level 0/4 to 20 mA (scalable)
Input resistance, R
i
approx. 200 Ω
Max. current 30 mA
Resolution for analog inputs 10 bit (+ sign)
Accuracy of analog inputs Max. error 0.5% of full scale
Bandwidth 20 Hz/100 Hz
The analog inputs are galvanically isolated from the supply voltage (PELV) and other high-voltage terminals.
Mains
Functional
isolation
PELV isolation
Motor
DC-Bus
High
voltage
Control
+24V
RS485
18
37
130BA117.10
Figure 8.1 PELV Isolation
Specifications Instruction Manual