OPERATION INSTRUCTIONS DANFOSS ENG

Manual initialization procedure
1. Remove power to the unit and wait for the
display to turn off.
2. Press and hold [Status], [Main Menu], and [OK] at
the same time while applying power to the unit
(approximately 5 s or until audible click and fan
starts).
Factory default parameter settings are restored during
start-up. This may take slightly longer than normal.
Manual initialization does not reset the following
adjustable frequency drive information:
15-00 Operating hours
15-03 Power-ups
15-04 Over Temps
15-05 Over Volts
5.4 Basic Programming
5.4.1 Commissioning with SmartStart
The SmartStart wizard enables fast configuration of basic
motor and application parameters.
At first power-up or after initialization of the
adjustable frequency drive, SmartStart starts
automatically.
Follow on-screen instructions to complete
commissioning of the adjustable frequency drive.
Always reactivate SmartStart by selecting Quick
Menu Q4 - SmartStart.
For commissioning without use of the SmartStart
wizard, refer to chapter 5.4.2 Commissioning via
[Main Menu] or the Programming Guide.
NOTICE!
Motor data are required for the SmartStart set-up. The
required data are normally available on the motor
nameplate.
5.4.2 Commissioning via [Main Menu]
Recommended parameter settings are intended for start-
up and checkout purposes. Application settings may vary.
Enter data with power ON, but before operating the
adjustable frequency drive.
1. Press [Main Menu] on the LCP.
2. Press the navigation keys to scroll to parameter
group 0-** Operation/Display and press [OK].
130BP066.10
1107 RPM
0 - ** Operation/Display
1 - ** Load/Motor
2 - ** Brakes
3 - ** Reference / Ramps
3.84 A 1 (1)
Main Menu
Figure 5.2 Main Menu
3. Press navigation keys to scroll to parameter
group 0-0* Basic Settings and press [OK].
0-
**
Operation / Display
0.0%
0-0
*
Basic Settings
0-1
*
Set-up Operations
0-2
*
LCP Display
0-3
*
LCP Custom Readout
0.00A 1(1)
130BP087.10
Figure 5.3 Operation/Display
4.
Press navigation keys to scroll to 0-03 Regional
Settings and press [OK].
0-0
*
Basic Settings
0.0%
0-03 Regional Settings
[0] International
0.00A 1(1)
130BP088.10
Figure 5.4 Basic Settings
Commissioning Instruction Manual
26 Danfoss A/S © Rev. 11/06/2014 All rights reserved. MG11AK22