OPERATION INSTRUCTIONS DANFOSS ENG
8.4 Ambient Conditions
Environment
IP rating IP00/Chassis, IP20
1)
/Chassis, IP21
2)
/Type 1, IP54/Type 12, IP55/Type 12, IP66/Type 4X
Vibration test 1.0 g
Max. relative humidity 5%–93% (IEC 721-3-3; Class 3K3 (non-condensing) during operation
Aggressive environment (IEC 60068-2-43) H
2
S test
class Kd
Ambient temperature
3)
Max. 122°F [50°C] (24-hour average maximum 113°F [45°C])
Minimum ambient temperature during full-scale operation 32°F [0°C]
Minimum ambient temperature at reduced performance 14°F [-10°C]
Temperature during storage/transport -13°–+149/158°F [-25–+65/70°C]
Maximum altitude above sea level without derating 3,300 ft [1,000 m]
Derating for high altitude, see special conditions in the Design Guide.
EMC standards, Emission EN 61800-3
EMC standards, Immunity EN 61800-3
See section on special conditions in the Design Guide.
1) Only for
≤
3.7 kW (200–240 V),
≤
7.5 kW (400–480 V)
2) As enclosure kit for
≤
3.7 kW (200–240 V),
≤
7.5 kW (400–480 V)
3) Derating for high ambient temperature, see special conditions in the Design Guide
8.5 Cable Specifications
Cable lengths and cross-sections for control cables
1)
Max. motor cable length, shielded 500 ft [150 m]
Max. motor cable length, non-shielded 1,000 ft [300 m]
Maximum cross-section to control terminals, flexible/ rigid wire without cable end sleeves 1.5 mm
2
/16 AWG
Maximum cross-section to control terminals, flexible wire with cable end sleeves 1 mm
2
/18 AWG
Maximum cross-section to control terminals, flexible wire with cable end sleeves with collar 0.5 mm
2
/20 AWG
Minimum cross-section to control terminals 0.25 mm
2
/24 AWG
1) For power cables, see electrical data tables in chapter 8.1 Electrical Data.
8.6 Control Input/Output and Control Data
Digital inputs
Programmable digital inputs 4 (6)
1)
Terminal number 18, 19, 27
1)
, 29
1)
, 32, 33,
Logic PNP or NPN
Voltage level 0–24 V DC
Voltage level, logic'0' PNP <5 V DC
Voltage level, logic'1' PNP >10 V DC
Voltage level, logic '0' NPN
2)
>19 V DC
Voltage level, logic '1' NPN
2)
<14 V DC
Maximum voltage on input 28 V DC
Pulse frequency ranges 0–110 kHz
(Duty cycle) Min. pulse width 4.5 ms
Input resistance, R
i
Approx. 4 kΩ
Specifications Instruction Manual
MG11AK22 Danfoss A/S © Rev. 11/06/2014 All rights reserved. 59