Handbook OPTIMA R PC...BM 202207

34/44 | OPTIMA-R-PC...BM
Electrical Connections
AC/DC 24 V, modulating (Pressure control)
The ∆P controller operates with setpoint adjusted through analog input signal (terminal 3) and feedback signal
(terminal 5).
Y
U
2
1 3 6
7
5
DC (0) 2 V …10 V
DC (0) 2 V …10 V
8
D+
T
U
/
MP
+
T
T
~
+
~
Y
-D
Additional functions can be activated by connecting the override inputs z1 and z2.
The priority of these functions is higher than the ∆P modulating operation with analog input.
Override control z1
Contact 11-9 = Motor STOP
Contact 11-10 = Damper OPEN
Override control z2
Contact 12-13 = Damper CLOSED
Contact 12-14 = P
max
11 and 12 without contact = no priority override through z1 or z2
10
9
14
13
12
11
9
1110 12
13
14
15 16
z1
z2 S1
T
+
~
T
+
~
Priority rule - Analog ∆P control
1. z1
2. z2
3. a) adaption (autonomous initializing controller function)
4. b) synchronisation (autonomous initializing controller function)
5. Y-Modulating: P
min
... P
max
(through analog input)