MA FRICO SIRE COMPETENT FUNCTIONS FH GB 161117

SIRe Competent Fanheaters
9
External control
Heating settings
Filter guard settings
>Installer menu
>Installer menu>Filter guard
settings
Last filter change
Filter timer on/off
Filter timer setting
>Installer menu>Filter guard
settings
Filter timer setting
1500 h
>Installer menu>Filter guard
settings
Last filter change
Filter timer on/off
Filter timer setting
>Installer menu>Filter guard
settings
Filter timer setting
Last filter change
>Installer menu>Filter guard
settings
Last filter change
0 h
Filter timer on/off
GB
Filter guard settings
Unit with water heating
Filter alarm is displayed when the set Filter
time has been exceeded or when an external
filter guard is installed and triggered. Filter
timer can be used as a Service interval timer
for electrical heated units when filter is not
allowed.
Filter timer on/off
Filter alarm is activated by selecting On,
under Filter timer on/off.
Factory setting
Filter timer on/off: Off (On)
Filter timer setting
Under Filter timer setting, set the desired run
time to between 50 and 9950 hours.
Filter timer setting: 1500 h (50 - 9950 h)
Last filter change
To check the number of run time hours since
the last filter replacement, select Last filter
change. The time is reset when the filter
alarm is reset. If the time is to be reset before
the alarm has gone, switch the filter timer on
and off.