Handbook OPTIMA S FC BM 202206

17/34 | OPTIMA-S-FC...BM
Bus parameter
Tool
Authorisatio
n
Parameter/Function Unit/Value
Function/Description/
(Area)
Assistant
App
ZTH-EU Expert/OEM
Parametrisation – Communication
Bus protocol
BACnet MS/TP /
Modbus / MP
r/w E
Bus protocol BACnet MS/TP
MAC address 0...127 r/w E
Baudrate 9600 / ... / 115200 r/w E
Terminating resistor OFF/ON r/w E
Instance number 1...4194304 r/w E
Device name VAV universal (32 Z.) r/w E
Max master 1...127 r/w E
Bus protocol Modbus RTU
Address 1...247 r/w E
Baudrate 9600 / ... / 115200 r/w E
Terminating resistor OFF/ON r/w E
Parity
1-8-N-2/…E-1/…-O-1/…-
N-1
r/w E
Bus protocol Modbus RTU
MP address PP/MP1...8 PP (MP off)/MP1…8 r/w E
Bus fail position 0 0% … 100% (min…max) r/w E
Compatibility mode Default/VRP-M
Default: Belimo MP
datapool device
VRP-M: VRP-M
replacement in existing
MP system
r/w E
Legend
X Application supports function
r Tool: read
w Tool: write
Tool: Does not support parameter
E Only visible in Expert Mode Authorisations - functionally relevant settings are only accessible via the Expert Level
of the Belimo Assistant App.