Handbook OPTIMA S FC BM 202206

16/34 | OPTIMA-S-FC...BM
Configuration with ZTH-EU or by Belimo Assistant app via NFC or via Bluetooth through ZIP BT NFC
Parametrisation
Tool
Authorisatio
n
Parameter/Function Unit/Value
Function/Description/
(Area)
Assistant
App
ZTH-EU Expert/OEM
VAV Unit/Air Duct Pressure Control Butterly Valve - Manufacturer Parameters (OEM Values - Not Variable)
OSN Actuator xxxxx-xxxxx-xxx-xxx Actuator series number r
Rotation Direction CCW/CW
Actuator direction of
rotation setting
r/w E
Range of rotation Adapted/programmed
Actuator adapted/
programmed 30°...95°
r/w E
Power on behaviour
No action/synch. /
adaption
Actuator power on
behaviour
r/w E
Parametrisation - Project-specific Settings
Position Text string
Plant designation (64 Z./
ZTH 16 Z.)
r/w r
Max
m
3
/h | l/s | cfm (PC-tool/
ZTH %)
% (position)
Operating volumetric
flow 0% ... 100% V
nom
Damper position (pos.
ctrl.) 0% … 100%
r/w r/w
Min
m
3
/h | l/s | cfm (PC-tool/
ZTH %)
% (position)
Operating volumetric
flow 0% ... 100% V
nom
Damper position (pos.
ctrl.) 0% … 100%
r/w r/w
Altitude compensation ON/OFF Switch function ON/OFF r/w E
Altitude of installation 0 m
Compensated Δp and
volumetric flow values
to set the altitude of
installation (above sea
level)
r/w E
Function VAV-CAV/position control Control function r/w E
Room pressure cascade ON/OFF
VAV: secondary circuit
room pressure cascade
r/w E
Setpoint Analogue/bus
Analogue and hybrid
mode/bus
r/w E
Setpoint offset 0
VAV: ±5% compensation
ABL unit
r/w E
Reference signal Y
2 V ... 10 V/0 V ... 10 V/
adjustable
Setting for VAV control r/w E
Feedback type
Volumetric flow/Δp/
position
VAV: volume/Δp/damper
position
Pressure: Δp/damper
position
r/w E
Feedback U
2 V ... 10 V/0 V ... 10 V/
adjustable
Setting U signal r/w E