/34 | OPTIMA-S-FC...BM Table of Contents Description . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 3 Dimensions & Weights . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 10 Ordering Codes . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 13 Accessories . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
/34 | OPTIMA-S-FC...BM Description OPTIMA-S-FC...BM is a variable air volume controller with or without an insulation. The product is intended to control the flow volume of supply or return air. The product is installed into rectangular ducts. The product is ideal for all applications, where a variable air flow volume in ventilation, cooling or heating is required (offices, hotel rooms, meeting rooms, health care premisses, residentials, etc.
/34 | OPTIMA-S-FC...BM Design OPTIMA-S-FC...BM consists of a galvanized steel sheet casing, aluminium profile blades with rubber gaskets and a modular VAV control device. OPTIMA-SI-FC...BM is equipped by an insulation for sound reduction. The insulation is a 19 mm thick closed cell foam mat, protected by galvanized steel sheet. The casing contains a robust flanged mounting frame for installation into ducts. The blades are opposed action.
/34 | OPTIMA-S-FC...BM OPTIMA-S(I)-FC...
/34 | OPTIMA-S-FC...BM Pr (VA) P (W) LM24A-VST 90° 120 s - 4 2,5 NM24A-VST 90° 120 s - 6 3,5 LMQ24A-VST 90° 2,5 s - 25 14,5 NMQ24A-VST 90° 4s - 25 14,5 SMQ24A-VST 90° 7s - 28 16,5 NKQ24A-VST 90° 4s 4s 24 12,5 LF24A-VST 90° 120 s <20 s 7 4 NF24A-VST 90° 120 s <20 s 10 6,5 Legend Positioning angle Transition time Transition time without power supply (safety funcition) Pr (VA) Power rating (actuator + controller VRU...
/34 | OPTIMA-S-FC...BM Noise and thermal insulation material for OPTIMA-SI-FC...BM Base NBR/PVC Cellular Structure Closed Colour Black Density 80 kg/m 3 Water Absorption 2%<5% Resistence Air+ U.V.-Good Thermal Conductivity (t. + 40 °C) < 0,039 W/m K Class 1 (DM 26/06/84) UL 94-HF1 Fire Resistance Class 0 - BS 476 part6-7 UK NF certificate n.38 (until mm.32) France B-s3,d0 (EN 13501-1) Euroclass Marine and Shipbuilding MED B - MED D - DNV type approval Steam Diffusion MU > 7.
/34 | OPTIMA-S-FC...BM Modular Control/Actuator Unit Functionality Description Compact Control/ Actuator Unit Analog Input BUS Communication Parameters Hard Wired Feedback Setup Override Signal Feedback Values Main BUS Com. Variables Power Supply Read/write : Setpoint, Vmin, Vmax, OPEN, CLOSE BM-S BM-Q BM-QE BM-F DC 0 V (2 V) ... 10 V ModbusRTU Actual volume, ZTH-EU BACnet MS/ Damper OPEN, angle, BACnet MS/ ZIP-BT-NFC CLOSE, V , TP min TP DC 0(2) V ...
/34 | OPTIMA-S-FC...BM Product Parts OPTIMA-S-FC...BM H = 100, 200...1000 H = 150, 250...950 P2 P3 P5 P4 P6 P1 P7 OPTIMA-SI-FC...BM H = 100, 200...1000 P2 P8 P3 P5 P4 P6 P1 P7 Legend P1 Casing P2 Duct connection flanges P3 Damper blade with gasket P4 Measurement probe P5 Measurement impulse tubes P6 Modular control/actuator unit P7 Air flow transmitter P8 Insulation H = 150, 250...
/34 | OPTIMA-S-FC...BM Dimensions & Weights H = 100, 200...1000 OPTIMA-S(I)-FC...BM 310* H H+40 (W+44) (H+44)* W ≤95 BM-S ≤110 BM-Q ≤115 BM-QE ≤125 BM-F W+40 (mm) H = 150, 250...950 OPTIMA-S(I)-FC...
/34 | OPTIMA-S-FC...BM OPTIMA-S-FC...
/34 | OPTIMA-S-FC...
/34 | OPTIMA-S-FC...BM Ordering Codes OPTIMA-S-FC...BM Non-insulated VAV Controller OPTIMA-S-FC Nominal Size W×H OEM Belimo, Communication Type BM Switchable: Modbus-RTU or BACnet MS/TP or MP-Bus or analog setpoint/feedback DC 0 (2) V … 10 V Actuator Type S Standard actuator Q Actuator with short transition time QE Actuator with short transition time and electric safety function (only for sizes ≤ DN 400) F Actuator with mechanical safety function – spring return OPTIMA-SI-FC...
/34 | OPTIMA-S-FC...BM Example of the Ordering Code OPTIMA-SI-FC-400x300-BM-F Insulated VAV contoller, nominal size 400 mm x 300 mm, with spring return safety function actuator. NOTES: Standard setup of the control module is Modbus communication. Standard setup of the Vmin and Vmax is indicated in the Quick Selection table. It can be changed upon request, if requested as a note to the order.
/34 | OPTIMA-S-FC...BM Accessories ZTH-EU Handheld Tool ZTH-EU is a handheld tool for VAV controllers and communicative actuators. The product enables the customer to change the configuration of the VAV controllers. ZIP-BT-NFC Communication Port Bluetooth/NFC ZIP-BT-NFC is a wireless interface connecting the smartphone with configuration app Belimo Assistant via Bluetooth to the VAV controller VRU... with NFC communication protocol.
/34 | OPTIMA-S-FC...
/34 | OPTIMA-S-FC...BM Bus parameter Authorisatio n Tool Parameter/Function Unit/Value Function/Description/ (Area) Assistant App ZTH-EU Expert/OEM r/w – E Parametrisation – Communication Bus protocol BACnet MS/TP / Modbus / MP Bus protocol BACnet MS/TP MAC address 0...127 r/w – E Baudrate 9600 / ... / 115200 r/w – E Terminating resistor OFF/ON r/w – E Instance number 1...4194304 r/w – E Device name VAV universal r/w – E Max master 1...
/34 | OPTIMA-S-FC...BM Quick Selection NOTES: * Standard setup of the Vmin is adjusted corresponding to air flow velocity 2 m/s and standard setup of the Vmax is adjusted corresponding to air flow velocity 9 m/s. It can be changed upon request, if stated in the ordering code. The Vmin can be adjusted from 0 m3/h to Vnom value from the table below. The Vmax can be adjusted from 20 % to 100 % of the Vnom value from the table below.
/34 | OPTIMA-S-FC...
/34 | OPTIMA-S-FC...
/34 | OPTIMA-S-FC...
/34 | OPTIMA-S-FC...BM Technical Parameters Diagrams and technical parameters are available at design.systemair.
/34 | OPTIMA-S-FC...BM Installation OPTIMA-S(I)-FC...
/34 | OPTIMA-S-FC...BM Electrical Connections AC/DC 24 V, modulating (VAV) The VAV controller operates with setpoint adjusted through analog input signal (terminal 3) and feedback signal (terminal 5). ~ T – + Y U 2 T + ~ – 3 Y 5 6 U/ MP T 1 DC (0) 2 V …10 V DC (0) 2 V …10 V 7 8 D+ D- Additional functions can be activated by connecting the override inputs z1 and z2. The priority of these functions is higher than the VAV modulating operation with analog input.
/34 | OPTIMA-S-FC...BM AC/DC 24 V, contactor step control (CAV) The VAV controller operates with setpoint in discrete steps generated by different potentials connected to the analog input (terminal 3) and analog feedback signal (terminal 5). Contact 2-3 = Vmax 3 not connected = Vmin Contact 1-3 = damper CLOSE (control signal mode 2...10V) Contact 1-3 = Vmin (control signal mode 0...10 V) The control signal mode can be adjusted in the VAV controller by the handheld configuration tool ZTH-EU.
/34 | OPTIMA-S-FC...BM BACnet MS/TP or Modbus RTU (This operation mode requires parametrization) VAV control in Vmin … Vmax range and other functionalities with all variables communicated through bus (terminals 7, 8) – by Modbus or BACnet protocol. 2 ~ T – + + DC (0) 2 V …10 V DC (0) 2 V …10 V U 3 Y 5 6 U/ MP T T 1 Y ~ – GND D+ D- 7 8 D+ D- Additional functions can be activated by connecting the override inputs z1 and z2.
/34 | OPTIMA-S-FC...BM BACnet MS/TP or Modbus RTU with analog setpoint (hybrid mode) (This operation mode requires parametrization) VAV control in Vmin … Vmax range and other functionalities with setpoint reading through analog input (terminal 3) and feedback through analog output (terminal 5). All other variables are communicated through bus (terminals 7, 8) – by Modbus or BACnet protocol.
/34 | OPTIMA-S-FC...BM MP-Bus (This operation mode requires parametrization) VAV control in Vmin … Vmax range and other functionalities with all variables communicated through bus (terminals 1, 2, 5) – by MP-Bus protocol. ~ T – MP + A) 2 T + ~ – 3 Y 5 6 U/ MP T 1 7 8 D+ D- Additional functions can be activated by connecting the override inputs z1 and z2. The priority of these functions is higher than the VAV modulating operation with analog input.
/34 | OPTIMA-S-FC...BM Connection of passive sensor (Available in bus operation) The value measured by the passive sensor can be communicated as a variable by bus.
/34 | OPTIMA-S-FC...BM Connection of active sensor (Available in bus operation) The value measured by the active sensor can be communicated as a variable by bus. ~ ~ + S1 + z1 z2 – 10 11 12 13 14 15 16 T T – 9 Possible input voltage range: DC 0...
/34 | OPTIMA-S-FC...BM Connection switching contact (Available in bus operation) The binary value of the switching contact can be communicated as a variable by bus. ~ ~ + S1 + z1 z2 – 10 11 12 13 14 15 16 T T – 9 Requirements switching contact:The switch must be capable of switching a current of 10 mA @ 24 V cleanly.
/34 | OPTIMA-S-FC...BM Transport, Storage and Operation Transport and storage temperature range: -20 °C to +40 °C, dry indoor conditions. Opreration temperature range: -20 °C ... +70 °C in the duct, -20 °C ... +50 °C on the actuator.
/34 | OPTIMA-S-FC...BM Supplement Any deviations from the technical specifications contained herein and the terms should be discussed with the manufacturer. We reserve the right to make any changes to the product without prior notice, provided that these changes do not affect the quality of the product and the required parameters. Current information on all products is available on design.systemair.com.
Systemair DESIGN • 2022-06-24 • Handbook_OPTIMA_S_FC_BM_en-GB • E2516267-4D62-4E4F-BD2E-1764F775F266 • Original instructions