Handbook OPTIMA R FC BM 202204

6/43 | OPTIMA-R-FC...BM
Noise and thermal insulation material for OPTIMA-RI-FC...BM
Base NBR/PVC
Cellular Structure Closed
Colour Black
Density
80 kg/m
3
Water Absorption 2 % < 5 %
Resistence Air+ U.V.-Good
Thermal Conductivity (t. + 40 °C) < 0,039 W/m K
Class 1 (DM 26/06/84)
UL 94-HF1
Fire Resistance Class 0 - BS 476 part6-7 UK
NF certificate n.38 (until mm.32) France
B-s3,d0 (EN 13501-1) Euroclass
Marine and Shipbuilding MED B - MED D - DNV type approval
Steam Diffusion MU > 7.000
Noise Reduction (DIN 4109) Up to 30 dB
Ecological Compatibility NO CFC - HCFC, asbest free
Controls
The VAV controllers are equipped by OEM control module and actuator from Belimo. The control units are factory
calibrated as standard to the air volume control range V
min
... V
max
. The dimension table shows this standard setting.
Upon request the control range V
min
... V
max
can be adjusted to customized settings prior to dispatch. The air volumes
can also be re-adjusted on site with ZTH-EU hand held service tool. If specific air values for V
min
and V
max
would be
required, this must be indicated prior to order of the units for adequate calibration in the factory.