/43 | OPTIMA-R-FC...BM Table of Contents Description . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 3 Dimensions & Weights . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 9 Ordering Codes . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 11 Accessories . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
/43 | OPTIMA-R-FC...BM Description OPTIMA-R-FC...BM is a variable air volume controller with or without an insulation. The product is intended to control the flow volume of supply or return air. The product is installed into circular ducts of 80 mm up to 630 mm in diameter. The product is ideal for all applications, where a variable air flow volume in ventilation, cooling or heating is required (offices, hotel rooms, meeting rooms, health care premisses, residentials, etc.
/43 | OPTIMA-R-FC...BM Design OPTIMA-R-FC...BM is manufactured from galvanized steel sheet. The product consists of a casing, a duct connection with a rubber gasket, a damper blade with a rubber gasket and a modular VAV control device. OPTIMA-RI-FC...BM is equipped by an insulation for sound reduction. The insulation is a 19 mm thick closed cell foam mat, protected by galvanized steel sheet.
/43 | OPTIMA-R-FC...BM DN Tmax (Nm) 80 4 100 4 125 4 140 4 160 4 180 4 200 4 225 4 250 4 280 4 315 4 355 5 400 5 500 8 630 10 OPTIMA-R-FC...
/43 | OPTIMA-R-FC...BM Noise and thermal insulation material for OPTIMA-RI-FC...BM Base NBR/PVC Cellular Structure Closed Colour Black Density 80 kg/m 3 Water Absorption 2%<5% Resistence Air+ U.V.-Good Thermal Conductivity (t. + 40 °C) < 0,039 W/m K Class 1 (DM 26/06/84) UL 94-HF1 Fire Resistance Class 0 - BS 476 part6-7 UK NF certificate n.38 (until mm.32) France B-s3,d0 (EN 13501-1) Euroclass Marine and Shipbuilding MED B - MED D - DNV type approval Steam Diffusion MU > 7.
/43 | OPTIMA-R-FC...BM Modular Control/Actuator Unit Functionality Description Compact Control/ Actuator Unit Analog Input BUS Communication Parameters Hard Wired Feedback Setup Override Signal Feedback Values Main BUS Com. Variables Power Supply Read/write : Setpoint, Vmin, Vmax, OPEN, CLOSE BM-S BM-Q BM-QE BM-F DC 0 V (2 V) ... 10 V ModbusRTU Actual volume, ZTH-EU BACnet MS/ Damper OPEN, angle, BACnet MS/ ZIP-BT-NFC CLOSE, V , TP min TP DC 0(2) V ...
/43 | OPTIMA-R-FC...BM Product Parts OPTIMA-R-FC...BM... OPTIMA-RI-FC...BM...
/43 | OPTIMA-R-FC...BM Dimensions & Weights OPTIMA-R-FC...BM... (mm) øD 58 L2 45 45 ≤85 BM-S ≤100 BM-Q ≤100 BM-QE ≤115 BM-F L (mm) L1 øD øD1 58 OPTIMA-RI-FC...BM...
/43 | OPTIMA-R-FC...
/43 | OPTIMA-R-FC...BM Ordering Codes OPTIMA-R-FC...BM Non-insulated VAV Controller OPTIMA-R-FC Nominal Size DN OEM Belimo, Communication Type BM Switchable: Modbus-RTU or BACnet MS/TP or MP-Bus or analog setpoint/feedback DC 0 (2) V … 10 V Actuator Type S Standard actuator Q Actuator with short transition time QE Actuator with short transition time and electric safety function (only for sizes ≤ DN 400) F Actuator with mechanical safety function – spring return OPTIMA-RI-FC...
/43 | OPTIMA-R-FC...BM Example of the Ordering Code OPTIMA-RI-FC-125-BM-F Insulated VAV contoller, nominal size 125, with spring return safety function actuator. NOTES: Standard setup of the control module is Modbus communication. Standard setup of the Vmin and Vmax is indicated in the Dimensions and Weights table. It can be changed upon request, if requested as a note to the order.
/43 | OPTIMA-R-FC...BM Accessories ZTH-EU Handheld Tool ZTH-EU is a handheld tool for VAV controllers and communicative actuators. The product enables the customer to change the configuration of the VAV controllers. ZIP-BT-NFC Communication Port Bluetooth/NFC ZIP-BT-NFC is a wireless interface connecting the smartphone with configuration app Belimo Assistant via Bluetooth to the VAV controller VRU... with NFC communication protocol.
/43 | OPTIMA-R-FC...
/43 | OPTIMA-R-FC...BM Bus parameter Authorisatio n Tool Parameter/Function Unit/Value Function/Description/ (Area) Assistant App ZTH-EU Expert/OEM r/w – E Parametrisation – Communication Bus protocol BACnet MS/TP / Modbus / MP Bus protocol BACnet MS/TP MAC address 0...127 r/w – E Baudrate 9600 / ... / 115200 r/w – E Terminating resistor OFF/ON r/w – E Instance number 1...4194304 r/w – E Device name VAV universal r/w – E Max master 1...
/43 | OPTIMA-R-FC...
/43 | OPTIMA-R-FC...BM Technical Parameters Legend ps (Pa) Pressure drop qV (m3/h or l/s) LWA (dB(A)) LW (dB) Air flow volume A-weighted total radiated sound power level Non weighted total sound power level OPTIMA-R-FC-80-BM-F Pressure drop & A-weighted sound power level in dB(A) Pa 10 1000 20 30 40 50 l/s 70 dB(A) 80 dB(A) 800 600 60 dB(A) 400 200 50 dB(A) 50 qV pS m3/h Pa 36 OPTIMA-R(I)-FC-80-BM...
/43 | OPTIMA-R-FC...BM OPTIMA-R-FC-100-BM-F Pressure drop & A-weighted sound power level in dB(A) 25 Pa 1000 50 75 l/s 70 dB(A) 80 dB(A) 800 600 400 60 dB(A) 200 50 dB(A) 100 qV pS m /h Pa 3 57 OPTIMA-R(I)-FC-100-BM...
/43 | OPTIMA-R-FC...BM OPTIMA-R-FC-125-BM-F Pressure drop & A-weighted sound power level in dB(A) 40 Pa 1000 60 80 100 120 l/s 70 dB(A) 80 dB(A) 800 600 400 60 dB(A) 200 50 dB(A) 100 qV pS m /h Pa 3 88 OPTIMA-R(I)-FC-125-BM...
/43 | OPTIMA-R-FC...BM OPTIMA-R-FC-140-BM-F Pressure drop & A-weighted sound power level in dB(A) 50 Pa 1000 100 150 l/s 80 dB(A) 800 600 70 dB(A) 400 200 60 dB(A) 50 dB(A) 200 qV pS m /h Pa 3 111 OPTIMA-R(I)-FC-140-BM...
/43 | OPTIMA-R-FC...BM OPTIMA-R-FC-160-BM-F Pressure drop & A-weighted sound power level in dB(A) Pa 1000 50 100 150 200 l/s 80 dB(A) 800 600 70 dB(A) 400 200 60 dB(A) 50 dB(A) 250 qV pS m /h Pa 3 145 OPTIMA-R(I)-FC-160-BM...
/43 | OPTIMA-R-FC...BM OPTIMA-R-FC-180-BM-F Pressure drop & A-weighted sound power level in dB(A) 80 Pa 1000 120 160 200 240 280 l/s 80 dB(A) 800 600 70 dB(A) 400 200 60 dB(A) 50 dB(A) 200 qV pS m /h Pa 3 183 OPTIMA-R(I)-FC-180-BM...
/43 | OPTIMA-R-FC...BM OPTIMA-R-FC-200-BM-F Pressure drop & A-weighted sound power level in dB(A) 100 Pa 1000 200 300 l/s 80 dB(A) 800 600 70 dB(A) 400 200 60 dB(A) 50 dB(A) 400 qV pS m /h Pa 3 226 OPTIMA-R(I)-FC-200-BM...
/43 | OPTIMA-R-FC...BM OPTIMA-R-FC-225-BM-F Pressure drop & A-weighted sound power level in dB(A) Pa 1000 100 200 300 400 l/s 80 dB(A) 800 600 70 dB(A) 400 200 60 dB(A) 50 dB(A) 500 qV pS m /h Pa 3 286 OPTIMA-R(I)-FC-225-BM...
/43 | OPTIMA-R-FC...BM OPTIMA-R-FC-250-BM-F Pressure drop & A-weighted sound power level in dB(A) Pa 100 1000 200 300 400 500 l/s 80 dB(A) 800 600 70 dB(A) 400 200 60 dB(A) 50 dB(A) 500 qV pS m /h Pa 3 353 OPTIMA-R(I)-FC-250-BM...
/43 | OPTIMA-R-FC...BM OPTIMA-R-FC-280-BM-F Pressure drop & A-weighted sound power level in dB(A) 200 Pa 1000 300 400 500 600 l/s 80 dB(A) 800 600 70 dB(A) 400 200 60 dB(A) 50 dB(A) 500 qV pS m /h Pa 3 443 OPTIMA-R(I)-FC-280-BM...
/43 | OPTIMA-R-FC...BM OPTIMA-R-FC-315-BM-F Pressure drop & A-weighted sound power level in dB(A) 250 Pa 1000 500 750 l/s 80 dB(A) 800 600 400 70 dB(A) 200 60 dB(A) 1000 qV pS m /h Pa 3 561 OPTIMA-R(I)-FC-315-BM...
/43 | OPTIMA-R-FC...BM OPTIMA-R-FC-355-BM-F Pressure drop & A-weighted sound power level in dB(A) Pa200 1000 400 600 800 1000 l/s 800 80 dB(A) 600 400 70 dB(A) 200 60 dB(A) 50 dB(A) 1000 qV pS m /h Pa 3 713 OPTIMA-R(I)-FC-355-BM...
/43 | OPTIMA-R-FC...BM OPTIMA-R-FC-400-BM-F Pressure drop & A-weighted sound power level in dB(A) 400 Pa 1000 600 800 1000 1200 l/s 800 600 400 80 dB(A) 70 dB(A) 200 60 dB(A) 50 dB(A) 1000 qV pS m /h Pa 3 905 OPTIMA-R(I)-FC-400-BM...
/43 | OPTIMA-R-FC...BM OPTIMA-R-FC-500-BM-F Pressure drop & A-weighted sound power level in dB(A) Pa 1000 800 500 1000 1500 2000 l/s 80 dB(A) 600 400 70 dB(A) 200 60 dB(A) 50 dB(A) 2500 qV pS m /h Pa 3 1414 OPTIMA-R(I)-FC-500-BM...
/43 | OPTIMA-R-FC...BM OPTIMA-R-FC-630-BM-F Pressure drop & A-weighted sound power level in dB(A) 1000 Pa 1000 2000 3000 l/s 800 600 80 dB(A) 400 70 dB(A) 200 60 dB(A) 50 dB(A) m³/h 4000 qV pS m /h Pa 3 2244 OPTIMA-R(I)-FC-630-BM...
/43 | OPTIMA-R-FC...BM Installation (mm) OPTIMA-R-FC...BM...
/43 | OPTIMA-R-FC...BM Electrical Connections AC/DC 24 V, modulating (VAV) The VAV controller operates with setpoint adjusted through analog input signal (terminal 3) and feedback signal (terminal 5). ~ T – + Y U 2 T + ~ – 3 Y 5 6 U/ MP T 1 DC (0) 2 V …10 V DC (0) 2 V …10 V 7 8 D+ D- Additional functions can be activated by connecting the override inputs z1 and z2. The priority of these functions is higher than the VAV modulating operation with analog input.
/43 | OPTIMA-R-FC...BM AC/DC 24 V, contactor step control (CAV) The VAV controller operates with setpoint in discrete steps generated by different potentials connected to the analog input (terminal 3) and analog feedback signal (terminal 5). Contact 2-3 = Vmax 3 not connected = Vmin Contact 1-3 = damper CLOSE (control signal mode 2...10V) Contact 1-3 = Vmin (control signal mode 0...10 V) The control signal mode can be adjusted in the VAV controller by the handheld configuration tool ZTH-EU.
/43 | OPTIMA-R-FC...BM BACnet MS/TP or Modbus RTU (This operation mode requires parametrization) VAV control in Vmin … Vmax range and other functionalities with all variables communicated through bus (terminals 7, 8) – by Modbus or BACnet protocol. 2 ~ T – + + DC (0) 2 V …10 V DC (0) 2 V …10 V U 3 Y 5 6 U/ MP T T 1 Y ~ – GND D+ D- 7 8 D+ D- Additional functions can be activated by connecting the override inputs z1 and z2.
/43 | OPTIMA-R-FC...BM BACnet MS/TP or Modbus RTU with analog setpoint (hybrid mode) (This operation mode requires parametrization) VAV control in Vmin … Vmax range and other functionalities with setpoint reading through analog input (terminal 3) and feedback through analog output (terminal 5). All other variables are communicated through bus (terminals 7, 8) – by Modbus or BACnet protocol.
/43 | OPTIMA-R-FC...BM MP-Bus (This operation mode requires parametrization) VAV control in Vmin … Vmax range and other functionalities with all variables communicated through bus (terminals 1, 2, 5) – by MP-Bus protocol. ~ T – MP + A) 2 T + ~ – 3 Y 5 6 U/ MP T 1 7 8 D+ D- Additional functions can be activated by connecting the override inputs z1 and z2. The priority of these functions is higher than the VAV modulating operation with analog input.
/43 | OPTIMA-R-FC...BM Connection of passive sensor (Available in bus operation) The value measured by the passive sensor can be communicated as a variable by bus.
/43 | OPTIMA-R-FC...BM Connection of active sensor (Available in bus operation) The value measured by the active sensor can be communicated as a variable by bus. ~ ~ + S1 + z1 z2 – 10 11 12 13 14 15 16 T T – 9 Possible input voltage range: DC 0...
/43 | OPTIMA-R-FC...BM Connection switching contact (Available in bus operation) The binary value of the switching contact can be communicated as a variable by bus. ~ ~ + S1 + z1 z2 – 10 11 12 13 14 15 16 T T – 9 Requirements switching contact:The switch must be capable of switching a current of 10 mA @ 24 V cleanly.
/43 | OPTIMA-R-FC...BM Transport, Storage and Operation Transport and storage temperature range: -20 °C to +40 °C, dry indoor conditions. Opreration temperature range: -20 °C ... +70 °C in the duct, -20 °C ... +50 °C on the actuator.
/43 | OPTIMA-R-FC...BM Supplement Any deviations from the technical specifications contained herein and the terms should be discussed with the manufacturer. We reserve the right to make any changes to the product without prior notice, provided that these changes do not affect the quality of the product and the required parameters. Current information on all products is available on design.systemair.com.