Belimo Siemens Compact Comparison OPTIMA S202110
Belimo - Siemens compact comparison
Parameters/features
≡ Identical ≈ Similar
(no signicant difference)
≠ Entirely different
Belimo Siemens
Type
OPTIMA-S(SI)...BLC1 OPTIMA-S(SI)-FC...SA
Mechanical design,
sizes, casing, damper,
measurement probe,
connections, gaskets,
impulse tubing, insulation
≡
Tightness acc. to EN1751 4C/3C
≡
4C/3C
Q / ∆P / L
w
Parameters
(see design.systemair.com)
50 100 150 m³/h
10 20 30 40 50 l/s
250
500
750
1000
Pa
40 dB(A)
40 dB(A)40 dB(A)
50 dB(A)
50 dB(A)50 dB(A)
60 dB(A)
60 dB(A)60 dB(A)
70 dB(A)
70 dB(A)70 dB(A)
80 dB(A)
80 dB(A)80 dB(A)
≡
50 100 150 m³/h
10 20 30 40 50 l/s
250
500
750
1000
Pa
40 dB(A)
40 dB(A)40 dB(A)
50 dB(A)
50 dB(A)50 dB(A)
60 dB(A)
60 dB(A)60 dB(A)
70 dB(A)
70 dB(A)70 dB(A)
80 dB(A)
80 dB(A)80 dB(A)
VAV control parameters
& adjustment ranges
V
min
, V
max
, V
nom
≡
V
min
, V
max
, V
nom
Typical control error ±5 %
≡
±5 %
Setpoint & feedback
signal type
DC 0 V ... 10 V, 2 V ... 10 V
≡
DC 0 V ... 10 V, 2 V ... 10 V
Choice of feedback
information
on analog output
Air ow, pressure, damper position
≡
Air ow, pressure, damper position
BUS interface MP-Bus
≠
-
Power supply DC 24 V, AC 24 V
≈
AC 24 V
Power consumption < 5 VA
≈
< 5 VA
Actuator typical
transition time
120 s
≈
150 s
Override modes
(hard-wired)
Open, Close, V
min
, V
max
≡
Open, Close, V
min
, V
max
Override modes
(BUS)
Open, Close, V
min
, V
max
(only in MP-Bus mode)
≠
-
Handheld
conguration tool
Belimo ZTH-EU
≈
Siemens AST20