Handbook OPTIMA S FC 202201

11/26 | OPTIMA-S-FC, Siemens Equipment
Online View
Setpoint: Flow/pos. display of actual setpoint (depends on operating mode)
Actual flow: in % and m
3
/h (or l/s)
Actual position: Actual relative damper position
Diff. Pressure: Actual differential pressure in Pa
Override control: Off, Open, Close, Stop, Setpoint
Field Device Configuration
V
min
V
max
U-signal: Setting for the 0 V/2 V ... 10 V feedback signal to flow or position (only type SA)
Range: Y-signal setting the signal range to 0 V ... 10 V or 2 V ... 10 V (only type SA)
Range: U-signal setting the signal range to 0 V ... 10 V or 2 V ... 10 V (only type SA)
Altitude level: Altitude level in 100 m steps
Unit vol. flow m
3
/h or l/s
Unit V
min
& V
max
display V
min
/ V
max
in absolute (m
3
/h / l/s) or in relative units (%)
BUS Configuration (only types SM, SB)
Address: Address for RS-485 networks (Modbus/BACnet MS/TP)
Baud rate: Baud rate
Transmission format: Start-/Stopbit, Parity
Termination: Termination electronically switchable
Backup Mode: Setpoint monitoring On or Off
Backup Position: Target position if backup mode entered
Backup Timeout: Setpoint monitoring waiting time
Diagnostics and Maintenance
Field device info: Basic information on connected device
Field device statistics: Counters and statistical data of connected device
OEM default settings: Reset to OEM settings/Read or set OEM settings (only in OEM access level)
AST20 Settings
Authorization level: Change from SVC level to OEM level (password required)
Handheld tool settings: Settings like language, brightness etc. and software version information
Enter/change OEM password: Entering password for OEM level, or changing password if in OEM level
Persistent OEM level: Make OEM level persistent - active after power-off of AST20. (only in OEM access level)
Logoff OEM: Leave OEM level (only in OEM access level)
Mass Configuration
Mass configuration: Activates mass configuration
Resume mass configuration: Resume mass conf. if parameters have been changed on a downloaded configuration
Address incrementation: Automatically incrementing the address when using mass configuration (only types SM, SB)