Communication Manual

APPENDIX EXCEL TABLE PRINTOUT
Access version: 4.6-1-00 rev. 2
Signal name
EXOL
Type
Modbus type
Modbu
s
addres
RW
Bacnet
Scale
factor
Unit
Function Description Release
Access variable list
More information can be found in the Communication Manual
VentActual.A_AlaPt(45)
L
Input Status Register (1x)
0055
R
BV, 20055
Alarm point
Malfunction sequence-C
VentActual.A_AlaPt(46)
L
Input Status Register (1x)
0056
R
BV, 20056
Alarm point
Malfunction sequence-D
VentActual.A_AlaPt(47) L Input Status Register (1x) 0057 R BV, 20057 Alarm point Malfunction sequence-E
VentActual.A_AlaPt(48)
L
Input Status Register (1x)
0058
R
BV, 20058
Alarm point
Malfunction sequence-F
VentActual.A_AlaPt(49) L Input Status Register (1x) 0059 R BV, 20059 Alarm point Malfunction sequence-G
VentActual.A_AlaPt(50) L Input Status Register (1x) 0060 R BV, 20060 Alarm point Malfunction sequence-H
VentActual.A_AlaPt(51)
L
Input Status Register (1x)
0061
R
BV, 20061
Alarm point
Malfunction sequence-I
VentActual.A_AlaPt(52) L Input Status Register (1x) 0062 R BV, 20062 Alarm point Malfunction sequence-J
VentActual.A_AlaPt(53)
L
Input Status Register (1x)
0063
R
BV, 20063
Alarm point
Filter alarm supply air
VentActual.A_AlaPt(54)
L
Input Status Register (1x)
0064
R
BV, 20064
Alarm point
Filter alarm extract air
VentActual.A_AlaPt(55) L Input Status Register (1x) 0065 R BV, 20065 Alarm point Alarm low air flow
VentActual.A_AlaPt(56)
L
Input Status Register (1x)
0066
R
BV, 20066
Alarm point
Freeze protection guard
VentActual.A_AlaPt(57)
L
Input Status Register (1x)
0067
R
BV, 20067
Alarm point
Defrosting guard exchanger
VentActual.A_AlaPt(58) L Input Status Register (1x) 0068 R BV, 20068 Alarm point Fire alarm
VentActual.A_AlaPt(59)
L
Input Status Register (1x)
0069
R
BV, 20069
Alarm point
Smoke alarm
VentActual.A_AlaPt(60)
L
Input Status Register (1x)
0070
R
BV, 20070
Alarm point
External stop
VentActual.A_AlaPt(61) L Input Status Register (1x) 0071 R BV, 20071 Alarm point External alarm
VentActual.A_AlaPt(62)
L
Input Status Register (1x)
0072
R
BV, 20072
Alarm point
Service stop
VentActual.A_AlaPt(63) L Input Status Register (1x) 0073 R BV, 20073 Alarm point Electric heater is overheated
VentActual.A_AlaPt(64) L Input Status Register (1x) 0074 R BV, 20074 Alarm point Warning freeze protection
VentActual.A_AlaPt(65)
L
Input Status Register (1x)
0075
R
BV, 20075
Alarm point
Low efficiency exchanger
VentActual.A_AlaPt(66) L Input Status Register (1x) 0076 R BV, 20076 Alarm point Defrosting alarm
VentActual.A_AlaPt(67)
L
Input Status Register (1x)
0077
R
BV, 20077
Alarm point
Rotary exchanger alarm
VentActual.A_AlaPt(68)
L
Input Status Register (1x)
0078
R
BV, 20078
Alarm point
Extra alarm 1
VentActual.A_AlaPt(69) L Input Status Register (1x) 0079 R BV, 20079 Alarm point Extra alarm 2
VentActual.A_AlaPt(70)
L
Input Status Register (1x)
0080
R
BV, 20080
Alarm point
Extra alarm 3
VentActual.A_AlaPt(71)
L
Input Status Register (1x)
0081
R
BV, 20081
Alarm point
Extra alarm 4
VentActual.A_AlaPt(72) L Input Status Register (1x) 0082 R BV, 20082 Alarm point Extra alarm 5
VentActual.A_AlaPt(73)
L
Input Status Register (1x)
0083
R
BV, 20083
Alarm point
Extra alarm 6
VentActual.A_AlaPt(74) L Input Status Register (1x) 0084 R BV, 20084 Alarm point Extra alarm 7
VentActual.A_AlaPt(75) L Input Status Register (1x) 0085 R BV, 20085 Alarm point Extra alarm 8
VentActual.A_AlaPt(76)
L
Input Status Register (1x)
0086
R
BV, 20086
Alarm point
Extra alarm 9
VentActual.A_AlaPt(77) L Input Status Register (1x) 0087 R BV, 20087 Alarm point Extra alarm 10
VentActual.A_AlaPt(78)
L
Input Status Register (1x)
0088
R
BV, 20088
Alarm point
Internal battery error
VentActual.A_AlaPt(79)
L
Input Status Register (1x)
0089
R
BV, 20089
Alarm point
Alarm service interval
VentActual.A_AlaPt(80) L Input Status Register (1x) 0090 R BV, 20090 Alarm point Restart blocked after power on
VentActual.A_AlaPt(81)
L
Input Status Register (1x)
0091
R
BV, 20091
Alarm point
Deviation alarm supply air temperature
VentActual.A_AlaPt(82)
L
Input Status Register (1x)
0092
R
BV, 20092
Alarm point
Deviation alarm supply air fan
VentActual.A_AlaPt(83) L Input Status Register (1x) 0093 R BV, 20093 Alarm point Deviation alarm extract air fan
VentActual.A_AlaPt(84)
L
Input Status Register (1x)
0094
R
BV, 20094
Alarm point
Deviation alarm humidity control
VentActual.A_AlaPt(85)
L
Input Status Register (1x)
0095
R
BV, 20095
Alarm point
Deviation alarm extra controller
VentActual.A_AlaPt(86) L Input Status Register (1x) 0096 R BV, 20096 Alarm point High supply air temperature
VentActual.A_AlaPt(87)
L
Input Status Register (1x)
0097
R
BV, 20097
Alarm point
Low supply air temperature
VentActual.A_AlaPt(88) L Input Status Register (1x) 0098 R Alarm point Supply air temperature max limit
VentActual.A_AlaPt(89) L Input Status Register (1x) 0099 R Alarm point Supply air temperature min limit
VentActual.A_AlaPt(90)
L
Input Status Register (1x)
0100
R
Alarm point
High room temperature
VentActual.A_AlaPt(91) L Input Status Register (1x) 0101 R Alarm point Low room temperature
VentActual.A_AlaPt(92)
L
Input Status Register (1x)
0102
R
Alarm point
High extract air temperature
VentActual.A_AlaPt(93)
L
Input Status Register (1x)
0103
R
Alarm point
Low extract air temperature