Table of contents Chapter 1 About this document __________________________________________________________4 Introduction _______________________________________________________________________________ 4 Software version ___________________________________________________________________________ 4 Signal types _______________________________________________________________________________ 4 Chapter 2 System integration ___________________________________________________________6 Modbus _____________________
Chapter 1 About this document Introduction This document describes Access controller application communication possibilites in terms of integration as communication slave via EXOline, Modbus and BACnet. Software version Access version Available V4.0-1-04 Modbus are available V4.0-1-05 EXOline, BACnet and Modbus are available later NaviPad 1.1.0.
Supported Modbus functions: 1 = Read Coils 2 = Read Discrete Input 3 = Read Holding Register 4 = Read Input Register 5 = Write Single Coil 6 = Write Single Register 15 = Write Multiple Coils 16 = Write Multiple Registers BACnet type The BACnet type of signals: 10XXX = Read and write binary 20XXX = Read binary 30XXX = Read and write analogue 40XXX = Read analogue 30XXX = Read and write multistate 40XXX = Read multistate (Where XXX = Modbus address) NOTE: In the variable lists contained in this manual, the
Chapter 2 System integration Modbus Addresses All addresses starts with 0, and due to that some Master devices starts address with 1 (equal to register) it’s in that case necessary to add all addresses in this document with +1. Communication limitations The Modbus master must wait for a minimum of 3.5 character times (4 ms at 9600 bps) between two messages.
When using Modbus TCP the controller Ethernet port in combination with TCP port setting 502 should be used. Writing values To override the output values, set the output to manual mode using a Modbus signal. Then set the corresponding ..._ManSet signal to the wanted level. These signals are listed in Chapter 5: Holding Registers. Remember that only values with a default value are adjustable, you will find these in the chapters Coil Status Register and Holding Register.
BACnet Access from software version 4.0-1-05 is capable of communication via the BACnet-ASC (Application Specific Controller) protocol and from 4.3-1-00 with BACnet AAC (Advanced Application Controller). In order to connect a Access application to a BMS (Building Management System) via BACnet/IP use the TCP/IP port. BACnet/IP configuration (Activation status of BACnet/IP protocol) Upon delivery, the BACnet/IP protocol is disabled as a default.
DHCP The Dynamic Host Configuration Protocol (DHCP) is a network protocol used on Internet Protocol (IP) networks for dynamic distribution of network configuration parameters, such as IP addresses, DNS servers and other services. The Access controller can be configured to either obtain an IP address from a DHCP server (dynamic) or the address can be set manually (static).
Watchdog Access from software version 4.1-1-00 is capable of supervising communication recieved from a BMS master. One slave communication protocol can be monitored at a time. If no active communication from the BMS master is detected before the watchdog timeout elapses, an alarm message is generated. BMS watchdog (Activation of protocol) Upon delivery, the BMS watchdog is disabled as default.
Ethernet setting When NaviPad and Control unit are connected directly to each other via switch module without any DHCP server they assign themselves with Auto-IP (Link-local) addresses and then randomly pick from address range 169.254.x.y (255.255.0.0). The possibility of using a static IP address as alternative to a dynamic IP address (DHCP) is available from Access software version 4.0-1-04 and NaviPad software version 1.1.0.184.
Access controller The below picture illustrates the appearance of Ethernet settings for controller in controller web menu from Access software version 4.0-1-04: NaviPad The below picture illustrates the appearance of Ethernet settings for the NaviPad from NaviPad software version 1.1.0.
Chapter 2 │System integration 13
Type example addresses Example of useful register addresses in a flow chart for a AHU with rotary exchanger and a cooling unit. Tables of variables with register addresses Tables with communication variables and register addresses from document version (A010) are available as printout, see APPENDIX, and as a MS Excel file attached to this PDF. To access the attached Excel workbook, this document has to be opened with a dedicated PDF reader application (e.g. free version of Adobe Reader).
APPENDIX │APPENDIX 15
APPENDIX EXCEL TABLE PRINTOUT Access variable list Access version: 4.6-1-00 VentSettings.S_AlaAcknowAll VentSettings.S_FilterAlarmReset AlaData.Ala_MalfunctionSAF1_Status L L X Coil Status Register (0x) Coil Status Register (0x) Input Register (3x) 0000 RW BV, 10000 0001 RW BV, 10001 0000 R AlaData.Ala_MalfunctionSAF2_Status AlaData.Ala_MalfunctionSAF3_Status AlaData.Ala_MalfunctionSAF4_Status AlaData.Ala_MalfunctionSAF5_Status AlaData.Ala_MalfunctionEAF1_Status AlaData.
APPENDIX EXCEL TABLE PRINTOUT Access variable list Access version: 4.
APPENDIX EXCEL TABLE PRINTOUT Access variable list Access version: 4.
APPENDIX EXCEL TABLE PRINTOUT Access variable list Access version: 4.
APPENDIX EXCEL TABLE PRINTOUT Access variable list Access version: 4.
APPENDIX EXCEL TABLE PRINTOUT Access variable list Access version: 4.
APPENDIX EXCEL TABLE PRINTOUT Access variable list Access version: 4.
APPENDIX EXCEL TABLE PRINTOUT Access variable list Access version: 4.
APPENDIX EXCEL TABLE PRINTOUT Access variable list Access version: 4.6-1-00 Scale factor Bacnet Modbus type VentActual.A_UnitMode X Input Register (3x) 0396 R MSV, 40396 1 VentActual.A_UnitModeControl X Input Register (3x) 0397 R MSV, 40397 1 Unit information VentActual.A_ActiveSeqType X Input Register (3x) 0398 R MSV, 40398 1- Unit information VentActual.A_ActiveHeatSeqStep VentActual.A_ActiveCoolSeqStep VentActual.
APPENDIX EXCEL TABLE PRINTOUT Access variable list Access version: 4.6-1-00 VentActual.A_Y5Sequence VentActual.A_Y6Sequence VentActual.A_Y7Sequence VentActual.A_Y8Sequence VentActual.A_Y9Sequence VentActual.A_Y10Sequence VentActual.A_SAF VentActual.A_EAF VentActual.
APPENDIX EXCEL TABLE PRINTOUT Access variable list Access version: 4.
APPENDIX EXCEL TABLE PRINTOUT Access variable list Access version: 4.
APPENDIX EXCEL TABLE PRINTOUT Access variable list Access version: 4.6-1-00 Scale factor Bacnet Modbus type VentComActual.CA_MotorCurrentSAF(8) VentComActual.CA_MotorCurrentEAF(6) VentComActual.CA_MotorCurrentEAF(7) VentComActual.CA_MotorCurrentEAF(8) VentComActual.CA_MotorPowerSAF(6) VentComActual.CA_MotorPowerSAF(7) VentComActual.CA_MotorPowerSAF(8) VentComActual.CA_MotorPowerEAF(6) VentComActual.CA_MotorPowerEAF(7) VentComActual.CA_MotorPowerEAF(8) VentComActual.CA_ActiveFaultSAF(6) VentComActual.
APPENDIX EXCEL TABLE PRINTOUT Access variable list Access version: 4.
APPENDIX EXCEL TABLE PRINTOUT Access variable list Access version: 4.
APPENDIX EXCEL TABLE PRINTOUT Access variable list Access version: 4.
APPENDIX EXCEL TABLE PRINTOUT Access variable list Access version: 4.
APPENDIX EXCEL TABLE PRINTOUT Access variable list Access version: 4.
APPENDIX EXCEL TABLE PRINTOUT Access variable list Access version: 4.
APPENDIX EXCEL TABLE PRINTOUT Access variable list Access version: 4.
APPENDIX EXCEL TABLE PRINTOUT Access variable list Access version: 4.6-1-00 TimeHp.Posts(19).FromDate TimeHp.Posts(19).ToDate TimeHp.Posts(20).FromDate TimeHp.Posts(20).ToDate TimeHp.Posts(21).FromDate TimeHp.Posts(21).ToDate TimeHp.Posts(22).FromDate TimeHp.Posts(22).ToDate TimeHp.Posts(23).FromDate TimeHp.Posts(23).ToDate TimePro.
APPENDIX EXCEL TABLE PRINTOUT Access variable list Access version: 4.
APPENDIX EXCEL TABLE PRINTOUT Access variable list Access version: 4.
APPENDIX EXCEL TABLE PRINTOUT Access variable list Access version: 4.
APPENDIX EXCEL TABLE PRINTOUT Access variable list Access version: 4.
APPENDIX EXCEL TABLE PRINTOUT Access variable list Access version: 4.6-1-00 AlaData.Ala_MalfunctionHeatingZone2_DelayValue AlaData.Ala_MalfunctionHeatingZone3_DelayValue AlaData.Ala_MalfunctionCoolingZone1_DelayValue AlaData.Ala_MalfunctionCoolingZone2_DelayValue AlaData.Ala_MalfunctionCoolingZone3_DelayValue AlaData.Ala_ControlErrorSupplyTempZone1_DelayValue AlaData.Ala_ControlErrorSupplyTempZone2_DelayValue AlaData.Ala_ControlErrorSupplyTempZone3_DelayValue AlaData.
APPENDIX EXCEL TABLE PRINTOUT Access variable list Access version: 4.6-1-00 VentSettings.S_AirFlowX(13) VentSettings.S_AirFlowK(14) VentSettings.S_AirFlowX(14) VentSettings.S_AirFlowK(15) VentSettings.S_AirFlowX(15) VentSettings.S_DOSelect_SeqPumpY1(0) R R R R R X Holding Register (4x) Holding Register (4x) Holding Register (4x) Holding Register (4x) Holding Register (4x) Holding Register (4x) 0544 0545 0546 0547 0548 0549 AV, 30544 AV, 30545 AV, 30546 AV, 30547 AV, 30548 MSV, 30549 VentSettings.
APPENDIX EXCEL TABLE PRINTOUT Access variable list Access version: 4.6-1-00 VentSettings.S_DOSelect_ChangeOver1 X Holding Register (4x) 0563 RW MSV, 30563 VentSettings.S_DOSelect_ChangeOver2 X Holding Register (4x) VentSettings.S_AirUnitAutoMode X VentSettings.
APPENDIX EXCEL TABLE PRINTOUT Access variable list Access version: 4.6-1-00 VentSettings.S_SAFManualOutput VentSettings.S_EAFAutoMode R X Holding Register (4x) Holding Register (4x) 0569 RW AV, 30569 0570 RW MSV, 30570 VentSettings.S_EAFManualSetpoint VentSettings.S_EAFManualOutput VentSettings.S_ExternalControl R R X Holding Register (4x) Holding Register (4x) Holding Register (4x) 0571 RW AV, 30571 0572 RW AV, 30572 0573 RW MSV, 30573 VentSettings.
APPENDIX EXCEL TABLE PRINTOUT Access variable list Access version: 4.6-1-00 Scale factor Bacnet Modbus type VentSettings.S_FanType X Holding Register (4x) 0586 RW MSV, 30586 VentSettings.S_SupplySetpoint R Holding Register (4x) 0588 RW AV, 30588 10 Temperature setting VentSettings.S_ExtractSetpoint VentSettings.S_SupplySetpointMax VentSettings.S_SupplySetpointMin VentSettings.S_SupplySetpOffsetLow VentSettings.S_SupplySetpOffsetHigh VentSettings.S_Curve1_X1 VentSettings.
APPENDIX EXCEL TABLE PRINTOUT Access variable list Access version: 4.
APPENDIX EXCEL TABLE PRINTOUT Access variable list Access version: 4.6-1-00 Scale factor Bacnet Modbus type VentSettings.S_EAFModeFreeCool X Holding Register (4x) 0654 RW MSV, 30654 VentSettings.S_EAFManSetpFreeCool VentSettings.S_EAFManOutFreeCool VentSettings.S_EAFModeFire R R X Holding Register (4x) Holding Register (4x) Holding Register (4x) 0655 RW AV, 30655 0656 RW AV, 30656 0657 RW MSV, 30657 10 P/Q 10 % 1 Operation override Operation override Operation override VentSettings.
APPENDIX EXCEL TABLE PRINTOUT Access variable list Access version: 4.6-1-00 VentSettings.S_SeqY3PID_ITime VentSettings.S_SeqY4PID_Pband VentSettings.S_SeqY4PID_ITime VentSettings.S_SeqY5PID_Pband VentSettings.S_SeqY5PID_ITime VentSettings.S_SeqY6PID_Pband VentSettings.S_SeqY6PID_ITime VentSettings.S_SeqY7PID_Pband VentSettings.S_SeqY7PID_ITime VentSettings.S_SeqY8PID_Pband VentSettings.S_SeqY8PID_ITime VentSettings.S_SeqY9PID_Pband VentSettings.S_SeqY9PID_ITime VentSettings.S_SeqY10PID_Pband VentSettings.
APPENDIX EXCEL TABLE PRINTOUT Access variable list Access version: 4.6-1-00 VentSettings.S_AOManual_SequenceY8 VentSettings.S_AOSelect_SequenceY9 R X Holding Register (4x) Holding Register (4x) 0732 RW AV, 30732 0733 RW MSV, 30733 VentSettings.S_AOManual_SequenceY9 VentSettings.S_AOSelect_SequenceY10 R X Holding Register (4x) Holding Register (4x) VentSettings.S_AOManual_SequenceY10 VentSettings.S_FreeCoolDayLimit R R VentSettings.S_FreeCoolHighLimit VentSettings.S_FreeCoolLowLimit VentSettings.
APPENDIX EXCEL TABLE PRINTOUT Access variable list Access version: 4.6-1-00 VentSettings.S_FrostProtSPStop(1) VentSettings.S_FrostProtPGain(1) R R Holding Register (4x) Holding Register (4x) 0770 RW AV, 30770 0771 RW AV, 30771 VentSettings.S_FrostProtSPRun(2) VentSettings.S_FrostProtSPStop(2) VentSettings.S_FrostProtPGain(2) R R R Holding Register (4x) Holding Register (4x) Holding Register (4x) VentSettings.S_ExtraControllerSetP VentSettings.S_ExtraControllerMode R X VentSettings.
APPENDIX EXCEL TABLE PRINTOUT Access variable list Access version: 4.6-1-00 VentSettings.S_RecircTempControl X Holding Register (4x) 0791 RW MSV, 30791 VentSettings.S_RecircMaxRoomTemp R Holding Register (4x) VentSettings.S_RecircFreeCool VentSettings.S_RecircSAFOffset VentSettings.S_RecircEAFOffset VentSettings.S_RecircSetPOffset VentSettings.S_FilterAlarmTime VentSettings.S_ExtraSensor1HighLimit(0) VentSettings.S_ExtraSensor2HighLimit VentSettings.S_ExtraSensor3HighLimit VentSettings.
APPENDIX EXCEL TABLE PRINTOUT Access variable list Access version: 4.6-1-00 Scale factor Bacnet Modbus type VentSettings.S_FanComp2X3 VentSettings.S_FanComp2Y3 VentSettings.S_FanComp3X1 VentSettings.S_FanComp3Y1 VentSettings.S_FanComp3X2 VentSettings.S_FanComp3Y2 VentSettings.S_FanComp3X3 VentSettings.S_FanComp3Y3 VentSettings.S_NeutralZone VentSettings.S_FreeCoolSAFOffset VentSettings.S_FreeCoolEAFOffset VentSettings.
APPENDIX EXCEL TABLE PRINTOUT Access variable list Access version: 4.6-1-00 VentSettings.S_FrostProtPGainZone2 R Holding Register (4x) 0869 RW AV, 30869 VentSettings.S_FrostProtSPRunZone3 VentSettings.S_FrostProtSPStopZone3 VentSettings.S_FrostProtPGainZone3 R R R Holding Register (4x) Holding Register (4x) Holding Register (4x) VentSettings.S_SAFLowspeedAirFlow(0) VentSettings.S_SAFNormalspeedAirFlow VentSettings.S_SAFHighspeedAirFlow VentSettings.S_EAFLowspeedAirFlow(0) VentSettings.
APPENDIX EXCEL TABLE PRINTOUT Access variable list Access version: 4.
APPENDIX EXCEL TABLE PRINTOUT Access variable list Access version: 4.
APPENDIX EXCEL TABLE PRINTOUT Access variable list Access version: 4.
APPENDIX EXCEL TABLE PRINTOUT Access variable list Access version: 4.
APPENDIX EXCEL TABLE PRINTOUT Access variable list Access version: 4.
APPENDIX EXCEL TABLE PRINTOUT Access variable list Access version: 4.
APPENDIX EXCEL TABLE PRINTOUT Access variable list Access version: 4.
Systemair Sverige AB SE-739 30 Skinnskatteberg, Sweden Phone +46 222 440 00 Fax +46 222 440 99 www.systemair.