Commissioning Record
Table Of Contents
Alarm configuration |
19
91
Low room temperature
- No action 30m 10°C
92
High extract air temperature
- No action 30m 30°C
93
Low extract air temperature
- No action 30m 10°C
94
High outdoor air temperature
- No action 30m 40°C
95
Low outdoor air temperature
-
No action 30m -30°C
96
Freeze protection alarm 1
A
Fast stop
1s
99
High limit extra sensor 1
-
No action 30m 30°C
100
Low limit extra sensor 1
-
No action 30m 10°C
101
High limit extra sensor 2
- No action 30m 30°C
102
Low limit extra sensor 2 - No action 30m 10°C
103
High limit extra sensor 3
- No action 30m 30°C
104
Low limit extra sensor 3 - No action 30m 10°C
105
High limit extra sensor 4
- No action 30m 30°C
106
Low limit extra sensor 4 - No action 30m 10°C
107
High limit extra sensor 5
- No action 30m 30°C
108
Low limit extra sensor 5 - No action 30m 10°C
109
High temperature selected sensor 1
- No action 0m 0°C
110
Low temperature selected sensor 1
-
No action 0m 0°C