Commissioning Record
Table Of Contents
Function settings
|
7
Function
Default setting Set value
Cooling
Type of cooler
□ None
□ Water
□ DX
None
Water
DX
Type of feedback, cooler
□ None
□ Alarm
□ Run indication
None
Alarm
Run indication
If water cooler
Pump control
□ None
□ Auto
□ Always running
None
Auto
Always running
Pump stop delay
5 min
min
If DX cooler
Reduction of min limit supply air temp
5 °C
°
Type of step control □ Sequential
□ Binary
Sequential
Binary
Number of steps
□ 1
□ 2
1
2
Temperature Zone 2 □ No
□ Yes
No
Yes
Temperature control type and set point □ Supply __________°C Supply °
□ Extract __________°C Extract
°
□ Room __________°C Room
°
Neutral zone
__________°C
°
If cascade control:
Min supply air temp. limit
__________°C
°
Max supply air temp. limit
__________°C
°
Heating
Type of heater
□ None
□ Water
□ Electric
None
Water
Electric
Type of feedback, heater
□ None
□ Alarm
□ Run indication
None
Alarm
Run indication
If water heater
Pump control
□ None
□ Auto
□ Always running
None
Auto
Always running
Pump stop delay
5 min
min
Pump running when outdoor temp. is
below:
10 °C
°
Hysteresis to allow pump stop
1 °C
°