TUNE-R-EX Damper for Explosive Atmosphere
/18 | TUNE-R-EX Table of Contents Description . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 3 Dimensions . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 8 Ordering Codes . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 10 Technical Parameters Installation . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
/18 | TUNE-R-EX Description TUNE-R-EX is a control and shut-off damper for ventilation in explosive hazardous atmosphere. The damper is available versions with actuator or a version with preparation for installation of an actuator and with manual adjustment lever. According to EN 1751 the tightness class of the damper C4 for duct static pressure up to 1000 Pa. Design The casing of the TUNE-R-EX and the damper blade and the actuator platform are made from galvanized steel.
/18 | TUNE-R-EX • M11 : Damper with stepless (0 V ... 10 V, 2/3 - Point) spring return actuator AC/DC 24 V ...
/18 | TUNE-R-EX The TUNE-R-EX has the following explosion hazardous atmosphere assignments: Version with preparation for installation of an actuator with manual adjustment lever TUNE-R-EX-dn-M0 FTZÚ 21 ATEX 0017X II 2 D Ex h IIIB T85°C Db II 2 G Ex h IIB T6 Gb Tamb = -20°C ... 70°C Versions with electric actuator TUNE-R-EX-dn-M3 TUNE-R-EX-dn-M6 TUNE-R-EX-dn-M10 TUNE-R-EX-dn-M11 FTZÚ 21 ATEX 0017X II 2 D Ex h IIIB T85°C Db II 2 G Ex h IIB T6 Gb Tamb = -20°C ...
/18 | TUNE-R-EX Product Parts TUNE-R-EX-...
/18 | TUNE-R-EX TUNE-R-EX-...
/18 | TUNE-R-EX Dimensions TUNE-R-EX-100...355-M0 12×3 DN-2 mm 45 45 80 L TUNE-R-EX-400...630-M0 8×8 DN-2 mm 45 45 87 L L mm TUNE-R-EX-...-M...
/18 | TUNE-R-EX TUNE-R-EX-100...355-M3/-M6/-M10/-M11 12×3 DN-2 mm 45 45 133 L TUNE-R-EX-400...630-M3/-M6/-M10/-M11 8×8 DN-2 mm 45 45 133 L L mm TUNE-R-EX-...-M...
/18 | TUNE-R-EX Ordering Codes Dimension (Nominal Diameter) 100 125 140 160 180 200 225 250 280 315 355 400 450 500 560 630 Product Type M0 Preparation for actuator with manual adjustment lever M3 Stepless (0 V ... 10 V, 2/3 - Point) actuator AC/DC 24 V ... 240 V, elevated ATEX classification for zone 1, 21, 2, 22 M6 Stepless (0 V ... 10 V, 2/3 - Point) spring return actuator AC/DC 24 V ... 240V, elevated ATEX classification for zone 1, 21, 2, 22 M10 Stepless ( 0 V ...
/18 | TUNE-R-EX Technical Parameters Pressure drop and radiated sound power level dependent on air flow volume.
/18 | TUNE-R-EX Pressure drop and radiated sound power level dependent on air flow volume.
/18 | TUNE-R-EX Pressure drop and radiated sound power level dependent on air flow volume.
/18 | TUNE-R-EX Installation ✓ TUNE-R-EX-...-M0 ✓ TUNE-R-EX-...-M3/-M6/-M10/-M11 360° ✓ TUNE-R-EX-...-M0 ✓ TUNE-R-EX-...-M3 ✓ TUNE-R-EX-...-M6 ✓ TUNE-R-EX-...-M10 ✓ TUNE-R-EX-...
/18 | TUNE-R-EX Modulating/3-pos. - with/without spring return 24...240 V AC/DC − + ~ ~ PE a 1 2 3 T YmA YV DC V DC/mA UmA UV DC b 4 5 1 2 3 4 5 6 PA Selection of running time for spring return:Spring return in ~ 10 s = standard wiring Spring return in ~ 3 s = additional wiring on terminal 5 Reverse function:Bridge 3 - 4 reverses the input and output signals Function and enforcement control of switch a and b in modulating mode: • a closed ForcedON (OFF) in acc.
/18 | TUNE-R-EX Modulating - with/without spring return (no feedback) 24...240 V AC/DC − + ~ ~ T YmA YV DC V DC/mA PE 1 2 3 4 5 1 2 3 4 5 6 PA Selection of running time for spring return:Spring return in ~ 10 s = standard wiring Spring return in ~ 3 s = additional wiring on terminal 5 Reverse function:Bridge 3 - 4 reverses the input and output signals 3-pos. - with/without spring return + feedback 24...
/18 | TUNE-R-EX Transport, Storage and Operation The damper cannot be installed carrying any mechanical loads from other structures. Dry indoor conditions with an operation temperature range of -20°C to +70°C in the duct, -20 °C ... +70 °C ambient temperature for the type TUNE-R-EX…M0 -20°C to +70°C in the duct, -20 °C ... +50 °C ambient temperature for the types TUNE-R-EX… M3, M6, M10, M11 Humidity up to 95% non-condensing conditions.
Systemair DESIGN • 2021-06-21 • Handbook_TUNE_R_EX_en-GB