Handbook TUNE R EX 202106

16/18 | TUNE-R-EX
Modulating - with/without spring return (no feedback)
Y
mA
Y
V DC
T
V DC/mA
24...240 V AC/DC
+
~
~
PE
1 2 3 54 61 2 3 54 PA
Selection of running time for spring return:Spring return in ~ 10 s = standard wiring
Spring return in ~ 3 s = additional wiring on terminal 5
Reverse function:Bridge 3 - 4 reverses the input and output signals
3-pos. - with/without spring return + feedback
U
mA
U
V DC
T
V DC/mA
24...240 V AC/DC
a b
+
~
~
PE
1 2 3 54 61 2 3 54 PA
Selection of running time for spring return:Spring return in ~ 10 s = standard wiring
Spring return in ~ 3 s = additional wiring on terminal 5
Reverse function:Bridge 3 - 4 reverses the input and output signals
3-pos. control mode:
a closed, b open - ON (OFF) in acc. to left/right mounting of actuator
b closed, a open - OFF (ON) in acc. to left/right mounting of actuator