Contents INTRODUCTION ............................................................................................................................. 5 EXPLANATION INPUT STEP VALUES.............................................................................................................. 5 EXPLANATION NUMBERS OF UNITS/VARIABLE/VARIANTS ETC. .......................................................................... 6 CHANGING OF VALUES ........................................................................
SYSTEM SETTINGS ............................................................................................................... 48 25.1 COMMUNICATION ....................................................................................................................... 48 25.2 NEW DEVICE .............................................................................................................................. 49 25.3 PREFERENCE UNIT SETTINGS ...............................................................
Version Document A001 Access V4.X Configuration manual Introduction This specification gives a general overview description of the software menu and web interface. Italic text in the left margin indicate an action, the following text describes the breadcrumb; the navigation path: Activate Configuration > Function Configuration > Function Activation If you click on breadcrumb, you will going up in menu structureTerminology Abbreviation terms for software specification.
Version Document A001 Access V4.X Configuration manual Explanation numbers of units/variable/variants etc. Varable Description Device 1 The first device in the list Device 2 Second device in the list Device n Some other number of all available numbers or rest of all available numbers in the list.
Version Document A001 Access V4.X Configuration manual Extract air cascade] Outdoor dependent supply air or room Outdoor dependent supply air or extract air Outdoor compensated room cascade Outdoor compensated extract air cascade Extract air depending supply air The supply air temperature is kept at the setpoint value by controlling the output signals for "Heating (Sequence-A)", "Exchanger (Sequence-B)", "Cooling (Sequence-C)", "Heating 2 (Sequence-G)” and “Cooling 2 (Sequence-H).
Version Document A001 Access V4.X Configuration manual When the outdoor temperature is lower than a settable limit (winter), outdoor compensated supply air temperature control will be active, otherwise (summer) cascaded room temperature control as in room cascade type. Outdoor dependent supply air or extract air Outdoor temperature dependent switching between supply air temperature control and extract air temperature control.
Version Document A001 Access V4.X Configuration manual Supply air temperature sensor No Yes Summer/Winter setpoints No Yes A special summer main setpoint (Supply/Extract/Room) can be activated by entering a supply setpoint at summer time: External setpoint device No TG-R4-PT100 TBI-PT1000 An external setpoint device, e.g. TBI-PT1000 or TG-R4/PT1000 can be connected. The setpoint device must follow the PT1000 resistance curve.
Version Document A001 Access V4.X Configuration manual Settings Frost protection (1/2/3) Settings for stopped and running mode Settings Exchanger & defrosting Step control settings for Step start/stop points, min switch time, outdoor temp/fan speed block of steps etc.) Step settings Fan heat/cool settings (Fan compensation) Pretreatment Fan control Activate: Configuration > Function Configuration > Function Activation Fan control type 1. 2. 3. 4. 5. 6. 7. 8.
Version Document A001 Access V4.X Configuration manual Manual Frequency controlled fans can be controlled at a fixed rotational speed. The rotational speed is selected by setting a fixed output signal (0 – 100%). Values for normal and reduced speed can be configured for each fan. Fans that are run with a fixed output signal can also be compensated (see the section above). In this mode, pressure sensors are not needed.
Version Document A001 Access V4.X Configuration manual transmitter (“Flow supply air”) is placed in the supply air fan cone, providing a measurement of the supply air flow. The supply air fan is controlled using the extract air flow as a setpoint. A scaling factor can be added if the supply air fan does not have the same characteristics as the extract air fan.
Version Document A001 Access V4.X Configuration manual Flow transmitter DESCRIPTION ∗ ,5 , Flow transmitter supply air K-factor X-factor Default 0,5 Flow transmitter extract air K-factor X-factor Default 0,5 Exchanger supply air pressure sensor K-factor X-factor Default 0.96…0.
Version Document A001 Access V4.X Configuration manual Adjustable range -100…100%. Example: Start Cooling If you want Cooling (Sequence-C / configured as DX) to start earlier than the PID loop, then set -10% in "Start cool" then will DX cooling start when Exchanger signal is 90% (PID loop signal for exchanger, if "cool recovery" = active).
Sequence Version Document A001 Access V4.
Version Document A001 Access V4.X Configuration manual Standby mode If frost protection is activated, the controller will go into ”Standby mode” when the running mode switches to ”Off”. The “Standby mode” will control the heating output to maintain a constant settable temperature at the frost protection sensor “Setpoint Standby mode”. Electric heating Control The heating is controlled using the analogue output and/or signal for start heating or step controller to control 1..4 digital output steps.
Version Document A001 Access V4.X Configuration manual Block step signal if alam Operation settings: No Yes Data & Settings > Temperature control > Heating (Heating 2) Sequential control Each output step has individually settable on and off values in percent of the control signal. The number of steps is equal to the number of heater/chiller groups. Minimum on and off times can be set, i.e. the minimum time the step has to be inactive or active for a change to occur.
Version Document A001 Access V4.X Configuration manual 3.
Version Document A001 Access V4.X Configuration manual Defrosting 1 Defrosting is activated either when the digital signal ”Defrosting” is activated or when the value of the analogue input ”Defrosting temperature” falls below the defrosting limit (-3°C), or when the analogue signal ”Exchanger extract air pressure sensor” rises above the set value for the current pressure.
3.3 Version Document A001 Access V4.X Configuration manual Cooler Activate: Configuration > Function Configuration > Function Activation> Sequence Configure type Activate extra cooler coil Example: Order cooling sequence: 1. ”Exchanger” 2. ”Cooler” 3.
Operation settings: Version Document A001 Access V4.X Configuration manual DX DX with exchanger control Data & Settings > Temperature control > Cooling (Cooling 2) Water cooler Control When the unit is in running mode the heating valve is controlled by the analogue output and digital output for pump control and/or signal for start heating. Pump indication A feedback from pump can be used, running indication or alarm indication.
Version Document A001 Access V4.X Configuration manual DX cooling with exchanger control When running cascade control, the supply air controller setpoint is normally controlled by the room/extract air controller output signal. When DX cooling is activated, the supply air controller setpoint is lowered to five degrees (adjustable) below the setpoint given by the room/extract air controller. This prevents the DX cooling from being activated/deactivated too often.
Version Document A001 Access V4.X Configuration manual settings. Therefore, Blocking step 1 will apply to binary steps 1 and 2, Blocking step 2 to binary steps 3 and 4, and Blocking step 3 to binary steps 5, 6 and 7. Blocking of DX cooling on cooling pump alarm Corrigo can be configured to block DX cooling on cooling pump alarm. In- and outputs Override of reduced speed for DX cooling Override to normal quantity of air for DX cooling when the unit runs on reduced quantity of air.
3.4 Version Document A001 Access V4.X Configuration manual Damper Activate: Configuration > Function Configuration > Function Activation> Sequence Configure type Activate Recirculation (Recirculation 2) Example: Order heating sequence: 1. ”Exchanger” 2. ”Heating” 3.
Version Document A001 Access V4.X Configuration manual Mixing dampers (Recirculation and/or Recirculation 2 dampers) Control The analogue output signal (”Recirculation 1” & “Recirculation 2”), control two dampers in separate sequence (“Recirculation 1” & “Recirculation 2”) for gradual mixing of outdoor air and recirculated air. In this mode the output signal decreases with increasing heat demand.
Version Document A001 Access V4.X Configuration manual Fan levels Activate Configuration > function Configuration > Function Activation Fan levels Normal Low-Normal Normal-High Low-Normal-High Select the fan stages to use in operation. The time settings in the scheduler show only the selected steps. Setpoints for Fans need to be updated.
Version Document A001 Access V4.X Configuration manual Fan compensation Activate: Configuration > Function Configuration > Function Activation Fan compensation No Yes Enables the fan compensation via temperature, pressure, CO2, RH sensor. There are 3 different compensation curves to use in the sub menu. Configure: Configuration > Function Configuration > Fan compensation There are three compensation functions called Fan compensation curve 1-3.
Version Document A001 Access V4.
Version Document A001 Access V4.X Configuration manual Minimum time for support control and demand control 20 min Extract air fan running during support control Operation settings: No Yes Data & Setings > Demand control > Support Control Support control is normally used when room temperature control or extract air control has been configured. When extract air control is configured a room sensor must be installed.
Version Document A001 Access V4.X Configuration manual In applications with varying occupancy the fan speeds or mixing dampers can be controlled by the air quality as measured by a CO2 sensor. With the CO2 function it’s possible to start and stop the fans, compensate the fan speed and in combination with mixing damper let in more outdoor air depending on the CO2 value.
Version Document A001 Access V4.X Configuration manual Yes Configure: There is no configurations settings, only operation settings on Free cooling Operation settings: Data & Settings > Demand Control > Free cooling This function is used during the summer to cool the building night-time using cool outdoor air, thereby reducing the need for cooling during the day and saving energy.
Configure: Version Document A001 Access V4.
Version Document A001 Access V4.X Configuration manual When the room temperature has fallen 1 K below the set max limit, recirculation will start again if the start conditions are still fulfilled. Frequency controlled fans and using recirculation control you can, depending on the type of fan control, configure a special pressure/flow offset for the setpoint or a manual output signal for the supply air fan.
Version Document A001 Access V4.X Configuration manual Outdoor air damper function when fire alarm Normal function (follow the fan) Always open Always closed Exhaust air damper function when fire alarm Normal function (follow the fan) Always open Always closed Fire dampers Fire dampers are normally configured to open (normally closed) on fire alarm. However, they can be configured to be normally open instead via NaviPad. Fire damper exercising Fire damper exercising can be configured.
Version Document A001 Access V4.
Version Document A001 Access V4.X Configuration manual Extract air fan setpoint type when smoke alarm Off/Auto normal setpoint Manual setpoint Manual outputs Low speed setpoint Normal speed setpoit High speed setpoint Manual setpoint or output (Extract air fan) 0..100% 0..
Version Document A001 Access V4.X Configuration manual Dehumidification An analogue output is used to control a dehumidifier. The output will increase on increasing humidity. A digital output can also be used to start a dehumidifier. Humidification/dehumidification An analogue output is used to control a humidifier. The output will increase on decreasing humidity. The cooling output Y3 will be activated for dehumidification through condensation. The output will increase on increasing humidity.
Version Document A001 Access V4.X Configuration manual followed at a pressure drop alarm. These are found under “Alarm configuration”. FS = X1:0 m3/h, Y1:10 Pa : X2:2000 m3/h, Y2:150 Pa. If a constant pressure drop alarm level is wanted, Y1 and Y2 should be set to the same value.
Configue: Version Document A001 Access V4.X Configuration manual Configuration > Function Configuration > Pretreatment Pretreatment activation during free cooling No Yes Control of dampers and pump for preheated or pre-cooled outdoor air via an underground intake channel.
Version Document A001 Access V4.X Configuration manual The extra controller can also be used for humidity control. The cooling battery will be used for dehumidification if the room/extract air humidity is too high. The function uses the sensor “Extra unit temp” and is placed immediately after the cooling battery. The function also requires use of a room humidity or extract air humidity sensor.
Version Document A001 Access V4.X Configuration manual Extra time channel 4 Stop delay motor control 1 0.. s Motor control 2 None Motor protection Run indication Mode motor control 2 Only Digital input Normal time channel Extra time channel 4 Stop delay motor control 2 Operation settings: 0..
Version Document A001 Access V4.X Configuration manual Alarm outputs None A/B-alarm A-alarm + B-alarm A-alarm + B/C-alarm 1 pcs Digital output 2 pcs digital outputs 2 pcs digital outputs Alarm priorities Alarms can be given different priority levels, A-alarm, B-alarm, C-alarm or not active. Digital outputs can be bound to act as alarm outputs for A/B-alarms on one digital output or both A- and B alarms (or B/C-alarm) on different digital ouptuts.
Version Document A001 Access V4.X Configuration manual related to any control functions. “Extra Sensor 1” should be used for external setpoint input. Extra alarm No Yes If selection are yes, 1..10 extra alarm can be configured under I/O allocation I/O allocation settings Configure: Configuration 22.
Version Document ID A001 Note! Access 4x Configuration manual If the sensor/signal is not in the list, please activate and configure the function and go back in this list to set up a physical position of I/O's Analouge inputs Device e.
Version Document ID A001 Note! Access_Function_description_B001.docx If you not finde your device, se 25.2 to configure/activate your device Signal Selecta I/O for signal on selected device. Note! It’s possible to select an already used I/O position. Please select the same ouputs as wiring diagram describe. Or select a free I/O’s position. 22.
Version A001 Document ID Access 4x Configuration manual Action No action Fast stop Normal stop Low speed Normal speed High speed Level A-alarm B-alarm C-alarm disabel Delay 0.. sec No. Alarm identity number Editable text Possible to change the alarm name Original text Not possible to change the original text Som alarms have alarm limits to set List of all alarm ID 1. 2. 3. 4. 5. 6. 7. 8. 9. 10. 11. 12. 13. 14. 15. 16. 17. 18. 19. 20. 21. 22. 23. 24. 25. 26. 27. 28. 29. 30.
79. 80. 81. 82. 83. 84. 85. 86. 87. 88. 89. 90. 91. 92. 93. 94. 95. 96. 97. 98. 99. 100. 101. 102. 103. 104. 105. 106. 107. 108. 109. 110. 111. 112. 113. 114. 115. 116. 117. 118. 119. 120. 121. 122. 123. 124. 125. 126. 127. 128. 129. 130. 131. 132. 133. 134. 135.
Version Document ID A001 Access 4x Configuration manual P-band I-time D-time System settings 25.
Version Document ID A001 Access 4x Configuration manual Baud rate Description 57k6 bps 57 600 bps 76k8 bps 76 800 bps 115k2 bps 115 200 bps Port 2 Port 3 Ethernet IP settings on Ethernet communication Cloud Enable cloudigo connection No Yes Serial number Unique serial number on the controller 25.2 New device Path: Configuration > System settings > Device List Device 1..
Version A001 Document ID Access 4x Configuration manual Function Configure: Model Configuration > System Settings > Device List > Device (n) > Functin > ….
Version A001 Document ID Access 4x Configuration manual 25.4 Save and restore Activate: Configuration > System Settings Save settings local No Yes Commissioning settings can be stored in a local memory.
Version A001 Document ID Access 4x Configuration manual Notes 52 (56) 2018-07-11