Compact air handling units Topvex SC, TC, SR, TR Commissioning Record Document in original language | 162527 · A004 GB
© Copyright Systemair AB All rights reserved E&OE Systemair AB reserves the rights to alter their products without notice. This also applies to products already ordered, as long as it does not affect the previously agreed specifications.
Contents 1 2 3 4 5 6 Commissioning record ......................................1 Notes and signatures .......................................1 Function settings.............................................2 3.1 Airflow.................................................2 3.2 Temperature .........................................3 3.3 Temperature (Zone control)......................6 3.4 General .............................................. 10 Setting the weekly program.............................
Commissioning record | 1 Commissioning record Company: Responsible: Customer: Date: Installation/Project: Installation address: Object/Unit: Model/Size: Item no.: Serial no: Access Software version: Time and date set: Operator password: 1111 Service password: 0612 Operator password changed: Service password changed: Weekly program set: External connections (sensors, dampers, external alarm etc.
2 | Function settings 3 Function settings 3.
Function settings | Fan compensation curves (configuration) Curve 1 Curve 2 Curve 3 Fan level All levels Low speed Normal speed High speed Low + Normal speed Normal + High speed All levels Low speed Normal speed High speed Low + Normal speed Normal + High speed All levels Low speed Normal speed High speed Low + Normal speed Normal + High speed Mode All modes When defrosting All modes When defrosting All modes When defrosting Fan Supply + Extract Supply Extract Supply + Extract Supply Extract
4 | Function settings Function Default setting Summer/Winter mode ⊠ No □ Yes Summer mode temperature set point □ Supply __________°C Supply ° □ Extract __________°C Extract ° □ Room __________°C Room ° Set value No Yes Switch between cascade control during Summer and outdoor compensated supply control during Winter □ No □ Yes No Yes Type of switch to indicate Summer □ Calender Calender From Date: Month: _____ _____ To Date: Month: _____ _____ Month: To Date: Month: Digita
Function settings | Function Default setting Set value If DX cooler Reduction of min limit supply air temp. when DX cooling 5 °C ° Min setpoint deviation to allow start of DX-cooling 2 °C ° Control function cooling □ 0-10 V □ Step controller 0-10 V Step controller Type of step control □ Sequential □ Binary Sequential Binary Number of steps □1 □2 □3 □4 1 2 3 4 Type of freeze protection □ None ⊠ Temp. sensor □ Guard None Temp.
6 | Function settings 3.3 Temperature (Zone control) Function Default setting Set value Zone control Zone control limitation ⊠ None □ Interlock heating/cooling None Interlock heating/cooling Temperature zone 1 ⊠ No □ Yes No Yes Temperature control type and set point □ Supply __________°C Supply ° □ Extract __________°C Extract ° □ Room __________°C Room ° __________°C ° Min supply air temp. limit __________°C ° Max supply air temp.
Function settings | Function Default setting Set value Cooling Type of cooler □ None □ Water □ DX None Water DX Type of feedback, cooler □ None □ Alarm □ Run indication None Alarm Run indication Pump control □ None □ Auto □ Always running None Auto Always running Pump stop delay 5 min min Reduction of min limit supply air temp 5 °C ° Type of step control □ Sequential □ Binary Sequential Binary Number of steps □1 □2 1 2 Temperature Zone 2 □ No □ Yes No Yes Temperature control type
8 | Function settings Function Default setting Freeze protection □ No □ Yes Alarm limit when unit is running 7 °C ° P-band when unit is running 5 °C ° Set point when unit is stopped 20 °C ° Set value No Yes Cooling Type of cooler □ None □ Water □ DX None Water DX Type of feedback, cooler □ None □ Alarm □ Run indication None Alarm Run indication Pump control □ None □ Auto □ Always running None Auto Always running Pump stop delay 5 min min Reduction of min limit supply air temp 5 °
Function settings | Function Default setting Set value If water heater Pump control □ None □ Auto □ Always running None Auto Always running Pump stop delay 5 min min Pump running when outdoor temp.
10 | Function settings 3.4 General Function Default setting Set value General Extended operation stop delay 0 min min Warm start when outdoor temp.
Function settings | Function Default setting Support control ⊠ No □ Yes Start heating room temperature 15 °C ° Stop heating room temperature 21 °C ° Start cooling room temperature 30 °C ° Stop cooling room temperature 28 °C ° Preheater ⊠ No □ Yes No Yes Start/Stop function ⊠ Unit running □ When defrosting Unit running When defrosting Preheater setpoint: -15 °C Exchanger defrosting mode (only applied for SC, TC units without section defrosting) ⊠ Pressure monitoring Pressure monitor
12 | Function settings Function Default setting Set value Exchanger defrosting mode (Only applied for SR/TR units) Temperature monitoring Temperature monitoring Setpoint min limit ° 4 °C Hysteresis to end defrosting ° 4 °C Min output during defrosting 40% % Stop supply air fan if outdoor temp < –100 °C ° Min time 5 min min Function Default setting Set value Fire function Operation mode when fire alarm ⊠ Stopped □ Continuous run □ Only supply air fan □ Only extract air fan □ Running v
Setting the weekly program | 4 Setting the weekly program Factory setting of the normal and low fan speed are: • High fan speed 00:00 to 00:00 Monday to Sunday. • Normal fan speed 07:00 to 16:00 Monday to Sunday. • Low fan speed 00:00 to 24:00 Monday to Sunday. • Settings of 00:00 to 00:00 stops the unit. E.g. changing low fan speed setting from 00:00-24:00 to 00:00-00:00 will stop the unit outside the time of normal fan speed.
14 | I/O Allocation 5 I/O Allocation Note any changes from the factory default input and output allocation configuration. Fill in any related information in the comment field. E.g. a pressure sensors measuring range, a contact’s polarity or similar.
I/O Allocation | Universal inputs UI1 UI2 UI3 UI4 162527 | A004 Function Comment 15
16 | Alarm configuration 6 Alarm configuration Alarm no.
Alarm configuration | Malfunction external heating/cooling (SEQ-J) B No action 5s Filter alarm supply air B No action 300s Filter alarm extract air B No action 300s Alarm low air flow A Normal stop 30s Freeze protection guard A Fast stop 1s Defrosting guard exchanger A Normal stop 30s Fire alarm A Fast stop 1s Smoke alarm A Fast stop 1s External stop C Normal stop 1s External alarm B No action 1s Service stop C Normal stop 1s Electric heater is overheated A Norm
18 | Alarm configuration Extra alarm 4 B No action 5s Extra alarm 5 B No action 5s Extra alarm 6 B No action 5s Extra alarm 7 B No action 5s Extra alarm 8 B No action 5s Extra alarm 9 B No action 5s Extra alarm 10 B No action 5s Internal battery error B No action 5s Alarm service interval C No action 1s Restart blocked after power on C Fast stop 0s Deviation alarm supply air temperature - No action 4m 5°C Deviation alarm supply air fan - No action 4m 500 D
Alarm configuration | Low room temperature - No action 30m 10°C High extract air temperature - No action 30m 30°C Low extract air temperature - No action 30m 10°C High outdoor air temperature - No action 30m 40°C Low outdoor air temperature - No action 30m -30°C Freeze protection alarm 1 A Fast stop 1s High limit extra sensor 1 - No action 30m 30°C Low limit extra sensor 1 - No action 30m 10°C High limit extra sensor 2 - No action 30m 30°C Low limit extra sensor 2
20 | Alarm configuration High temperature selected sensor 2 - No action 0m 0°C Low temperature selected sensor 2 - No action 0m 0°C Sensor error outdoor air temperature B No action 5s Sensor error intake air temperature B No action 5s Sensor error supply air temperature B No action 5s Sensor error exhaust air temperature B No action 5s Sensor error extract air temperature B No action 5s Sensor error room temperature 1 B No action 5s Sensor error room temperature 2 B No a
Alarm configuration | Sensor error freeze protection temperature 1 A Fast stop 1s Sensor error freeze protection temperature 2 A Fast stop 1s Sensor error freeze protection temperature 3 A Fast stop 1s Sensor error CO2 room/extract air B No action 5s Sensor error humidity room/extract air B No action 5s Sensor error humidity supply air B No action 5s Sensor error humidity outdoor B No action 5s Sensor error extra controller B No action 5s Signal error external control supply
22 | Alarm configuration Sensor error pressure filter extract air B No action 5s Sensor error efficiency temperature exchanger B No action 5s Communication fault device C No action 1s Malfunction extra controller B No action 5s Internal error A Fast stop 1s Service alarm smoke detector B No action 120s Sensor error smoke detector A Normal stop 5s Malfunction preheater B No action 5s Communcation fault BMS master C No action 1s Leakage heater valve B No action 5m Sens
Alarm configuration | Deviation alarm supply temp zone 2 B No action 30min 10°C Deviation alarm supply temp zone 3 B No action 30min 10°C Freeze protection alarm zone 1 A Fast stop 1s Freeze protection alarm zone 2 A Fast stop 1s Freeze protection alarm zone 3 A Fast stop 1s Electric heater is overheated zone 1 A Normal stop 1s Electric heater is overheated zone 2 A Normal stop 1s Electric heater is overheated zone 3 A Normal stop 1s Sensor error supply air temp zone 1 B
24 | Alarm configuration Sensor error freeze protection zone 2 A Fast stop 1s Sensor error freeze protection zone 3 A Fast stop 1s Signal error feedback cooler valve B No action 5s Signal error feedback outdoor air damper B No action 5s Signal error feedback recirc.
162527 | A004