Modbus Registers OPTIMA...GOMOD
Short instruction 227VM-024-05-MB
Written by: Michael Köhle Date: 13.11.2014 08:56:00 Side 8 of 13
2.1.3. Service Values
-r functions-code 0×03h -w functions-code 0×06h
Name
Address
decimal Data typ
Value
range r/w Description
memory
def.
value
Serial
number 1
100 WORD 101..9912 r serial number JJMM
EEPROM
-
serial
number 2
101 WORD 100..3123 r serial number DDHH
EEPROM
-
serial
number 3
102 WORD 01..59599 r serial number MMSSX
X = test number
EEPROM
-
software
version
103 WORD 1..65535 r software version
EEPROM
-
service
infor-
mation
104 WORD 0..65535 r see table status-register
RAM
min value
relative
105 WORD 0..10000 r/w min value [%] 0 .. 100.00
EEPROM
0
max val-
ue rela-
tive
106 WORD 0..10000 r/w max value [%] 0 .. 100.00
EEPROM
10000
sensor
type 1
107 WORD 0..4 r/w
sensor type
'0’ - - -
'1' active sensor [mV],
'2’ passive sensor [1k]
'3‘ *passive sensor [1…20k]
'4' *Digital 0/1
* not implemented
EEPROM
1
bus fail
position
108 WORD 0..2 r/w bus fail position
'0’ - - -
no bus monitoring
'1' at timeout position close
bus monitoring timeout 120s
'2’ at timeout position open
bus monitoring timeout 120s
EEPROM
0
min
value
absolute
120 WORD 0..65535 r/w min value [m³/h][l/s][pa]
EEPROM
0
max
value
absolute
121 WORD 0..65535 r/w max value [m³/h][l/s][pa]
EEPROM
98