technical documentation manuals 308013008

Electrical connection |
21
8.2.2 Wiring diagram
Important
Wrong connection can damage or destroy the motor.
Use the information on the nameplate to select the correct connection diagram.
Star / Delta Star / Delta
230 V
400 V
wiring_230/400V_180928_001
W2 U2 V2
U1 V1 W1
W2 U2 V2
U1 V1 W1
400 V
690 V
wiring_400/690V_190121_001
W2 U2 V2
U1 V1 W1
W2 U2 V2
U1 V1 W1
“1” Δ
“2” Y
“3” Thermal motor protection optional
“1” Δ
“2” Y
“3” Thermal motor protection optional
Two seperate windings
Dahlander
“1” Connection for low speed
“2” Connection for high speed
“3” Thermal motor protection optional
“1” Connection for low speed
“2” Connection for high speed
“3” Thermal motor protection optional
8.3 Frequency converter (if used)
Risk from resonant frequencies when using frequency
converter.
Only operate the fan outside these speed ranges.
Pass through these speed ranges so quickly that any
vibration cannot exceed the admissible resonant
frequency values.
For variable-speed fans, use a permanent vibration
monitoring for long-term safe operation.
Observe the operating instructions of the frequency
converter.
Commissioning of the frequency converter
Install the fan and frequency converter as near as
possible to one another.
Use shielded cables.
All components (fan, frequency converter and motor)
must be grounded.
We recommend using all-pole sinus filters.
Never exceed the maximum impeller rotation speed
indicated on the name plate of the fan.
Operation of the frequency converter
Heating of the motor due to use of a variable frequency drive must be checked in the application by the customer.
Avoid running the fan via the frequency converter below 10 Hz.
Starting time: min. 60 sec.
| 008