technical documentation manuals 308013008

14
| Installation
Mounting feet
Depending on the kind of fan and the construction size, mounting feet are either included in the delivery or available as
accessories. If you are not sure, check the online catalogue or contact Systemair.
Avoid resonance frequencies
Important
Risk of damage to the fan due to resonance frequencies
The minimum fan speed should be double the resonance frequency of the anti-vibration system
(vibration dampers).
To avoid resonance frequencies, see 8.3 Frequency converter (if used), page 21.
7.1 Vibration dampers
Important
Risk of damage to the fan due to incorrect vibration dampers
Use the vibration dampers suitable for the respective weight.
Use the vibration dampers with fire resistance classes that match the respective application.
Sylodyn vibration kit (if used)
The responsibility for the Sylodyn vibration kit installation is with the buyer/installer.
Important
Risk of damage to the fan due to incorrect installed vibration dampers
The fan shall rest entirely on the sylodyn anti vibration blocks. It is important that the fan is not pressed
against the mounting frame, therefore the minimum distance of 15 mm has to be kept, see following
picture.
1
Hexagonal head set screw
1
2
3
4
5
min. 15 mm
6
2
Sylodyn anti
vibration block
Available as Systemair accessory with a hole Ø
16mm
3
Safety plate Available as Systemair accessory with a hole Ø
16mm
4
Hexagonal nut
5
Mounting foot
6
Mounting frame
| 008