Manual Portier

Portier
9
Accessory Type
Control panel
CB22
Control panel
CB20
2-step Thermostat
RTI2
Door contact
MDC
Technical specifications Ambient, no heat - Portier A 1
Technical specifications
Electrical heat - Portier E 3
*
1
) Sound power (L
WA
) measurements according to ISO 27327-2: 2014, Installation type E.
*
2
) Sound pressure (L
pA
). Conditions: Distance to the unit 5 metres. Directional factor: 2. Equivalent absorption area:
200 m². At lowest/highest airflow.
*
3
) t = temperature rise of passing air at maximum heat output and highest airflow.
*
4
) Alternative 400 V3~ + 230 V~ (operating supply) if the current is greater than 16 A. Applies when connecting
several units.
Protection class: IP21.
CE compliant.
Type Output
steps
[kW]
Airflow
[m
3
/h]
t*
3
[°C]
Sound
power*
1
[dB(A)]
Sound
pressure*
2
[dB(A)]
Voltage
[V]
Amp.
[A]
Length
[mm]
Weight
[kg]
PS210E03 1,5/3 950/1200 10/8 66 44/50 230V~/400V3N~*
4
13,4/4,8 1020 17
PS210E06 3/6 950/1200 19/15 66 44/50 400V3N~*
4
9,2 1020 17
PS210E09 4,5/9 950/1200 28/23 66 44/50 400V3N~*
4
13,5 1020 17
PS215E09 4,5/9 1200/1900 23/14 66 39/50 400V3N~*
4
13,5 1530 24
PS215E14 6,7/13,5 1200/1900 34/21 66 39/50 400V3~
+ 230V~ 20,0 1530 24
Type Output
[kW]
Airflow
[m
3
/h]
Sound
power*
1
[dB(A)]
Sound
pressure*
2
[dB(A)]
Voltage
[V]
Amperage
[A]
Length
[mm]
Weight
[kg]
PS210A 0 1000/1300 70 44/54 230V~ 0,45 1020 14
PS215A 0 1300/2000 72 46/56 230V~ 0,55 1530 20