L BAL E263

7.8 Check sensor function
1. Program Mode
4.00 for pressure sensor.
2. Connect the voltage supply (+U
S
/ GND), disconnect output
0 ...10 V (A / GND).
3. Remove pressure hoses and measure output signal, nominal
= 0 V.
4. Create pressure at the "+" connection against the "-" connec-
tion (e. g. by carefully blowing in), measure the output signal
(0...10 V
measuring range).
5. If the sensor works, reconnect the pressure hoses and check
these if necessary.
8 Enclosure
8.1 Technical data
Type PCA1000D2 PCA6000D2
Part-No. 76739
(320064-42)
76740
(320065-42)
Voltage supply 10...24 V DC (+20 %)
Protected against reverse polarity
@ U
S
10 V DC @ U
S
13...24 V DC
Max. load output 0...10 V
(short-circuit-proof)
0.3 mA 10 mA
Max. current consumption ca. 6 mA 14 mA
Pressure connections +, - Hose connectors d = 5 / 6 mm (0.20 / 0.24 inch)
Housing PC (polycarbonate)
Fire protection classication UL94V0
Use position vertical (measuring depends on position)
Protection class IP54 according EN 60529
Weight approx. 230 g (0.50 lb)
Operating Instructions PCA1000/6000D2 Enclosure
L-BAL-E263-GB 1551 Index 001 Part.-No. 00163445-42
17/20