Modbus Registers OPTIMA...GOMOD

Short instruction 227VM-024-05-MB
Written by: Michael Köhle Date: 13.11.2014 08:56:00 Side 9 of 13
Name
Address
decimal Data typ
Value
range r/w Description
memory
def.
value
mode
signal
set point
analog
output
122 WORD 0..3 r/w
Value
Refer-
encing
signal
Analog
Out
EEPROM
0
0 Analog
In 1 [V]
0(2)…10
absolute
position
[V] 0 ..
10
1 commu-
nication
via
Modbus
register
0
absolute
position
[V] 0 ..
10
2 commu-
nication
via
Modbus
register
0
Value
register
10
3 Analog
IN 1 [V]
0(2)…10
Value
register
10
4 Analog
IN 1 [V]
6 ± 4
absolute
position
[V] 0 ..
10
5 Analog
IN 1 [V]
6 ± 4
Value
register
10
V
nom
200 WORD 0…30000 r/w volume nominal value [Pa]
0 ...300.00
EEPROM
25059
V
nom
unit/functi
on
201 WORD 0…5 r/w V
nom
unit EEPROM
4
Control function VAV
'0’ [l/s],
'1’ [m³/h]
Control function pressure:
'2 [Pa]
'3' [Wc]
Control function continuous:
'4' [°]
'5' [mm]