Modbus Registers OPTIMA...GOMOD

Short instruction 227VM-024-05-MB
Written by: Michael Köhle Date: 13.11.2014 08:56:00 Side 4 of 13
Function Description
Adr
(only ModBus)
Allows setting the address of the Modbus actuator, by turning the value
selector. It is possible to set the address from 1 up to 247.
If the value selector is turned to the end-stop "+" the
Display shows "2 in", this allows to select the
second level. If the second level is chosen, this is in-
dicated in the display by a small circle
In the second level the functions are as follows
Flow
Back to level one
V
min
V
btw
V
max
Not in use
Test Adaption drive is switched on.
Mode
Shows the actual position of the angel of rotation
(0…255 digital 0...100%)
Adr.
Allows to select the ModBus parameter
(see separate documentation)
V
nom
Allows to set the ModBus delay
(see separate documentation)
V
nom
Set-up of the V
nom
according to the flow corresponding to 1 inWC (250
Pa) differential pressure. The Setting of V
nom
is done in three stages
depending on value to be selected.
Stage I: 0…995 in steps of 5
Stage II: 1´000…9´950 in steps of 50
Stage II: 10´000…99´500 in steps of 500
Max. 18´000 l/s or 65´500 m³/h
For the first set-up no password is needed. After this first set-up one
needs to set first the password (255) and wait until the display flashes
and allows the setting of a different V
nom
.