DataSheet OPTIMA S202011

10 / 20 | Variable Air Volume Controllers
Ordering Code
Example of Ordering Code
OPTIMA-S-400x200-BLC1MOD-0
Rectangular VAV controller with Modbus-RTU and BACnet MS/TP communication on board.
V
min
= 576 m³/h V
max
= 2592 m³/h (default factory adjustment corresponding to min. 2 m/s and max. 9 m/s velocities).
Signal mode DC 0 V ... 10 V.
OPTIMA- - × - - - -
Single Skin Controller S
Double Skin Controller with Acoustic Insulation SI
200
...
Width W (mm) 1200
100
...
Height H (mm) 1000
BLC1
BLC4
BLC1MOD
BLC1LON
BLC1KNX
GO
Drive/Controller Type GOMOD
V
min
(m
3
/h)
V
max
(m
3
/h)
(DC 0 V ... 10 V) 0
Signal Mode (DC 2 V ... 10 V) 2
NOTES:
If not stated in the ordering code, the default V
min
will be adjusted corresponding to air ow velocity 2 m/s
and the default V
max
corresponding to velocity 9 m/s from factory.
If not stated in the ordering code, the signal mode default mode DC 2 V ... 10 V will be adjusted from factory.