Installation Sheet

subzero.com
|
5
Electrical
Installation must comply with all applicable electrical codes.
The electrical supply should be located within the shaded
area shown in the illustration below. A separate circuit,
servicing only this appliance is required. A ground fault cir-
cuit interrupter (GFCI) is not recommended and may cause
interruption of operation.
IMPORTANT NOTE: The electrical outlet must be placed so
the grounding prong is to the right of the thinner blades.
The outlet must be ush with the back wall.
ELECTRICAL REQUIREMENTS
Electrical Supply 115 VAC, 60 Hz
Service 15 amp
Receptacle 3-prong grounding-type
WARNING
Do not use an extension cord, two-prong adapter or
remove the power cord ground prong.
Preparation
To operate properly, the door must open a minimum of 90°.
Use a minimum 3"
(76) ller in corner installations to assure
a 90° door opening.
Uncrate the unit and inspect for damage. Remove and
recycle packing materials. Do not discard the kickplate, anti-
tip bracket, hardware and the leveling legs which hold the
wood base to the bottom of the unit.
Anti-Tip Bracket
WARNING
To prevent the unit from tipping forward, the anti-tip
bracket must be installed.
MODEL UW-24
The anti-tip bracket should be attached to the wall behind
the unit with the bracket ange located
1
/4" (6) above the top
of the unit. Refer to the illustration below. Failure to properly
position the anti-tip bracket will prevent proper engagement.
For installations that cannot accommodate the anti-tip
bracket, a countertop bracket is provided to secure the unit
to the countertop. Refer to the illustration below.
MODEL UW-24 / UW-24FS SITE PREPARATION
3" (76)
15
1
/2"
(394)
2"
(51)
LEFT SIDE
OF OPENING
FLOOR
Electrical supply location.
1
/4" (6)
ANTI-TIP
BRACKET
COUNTERTOP
BRACKET
Anti-tip bracket (UW-24).
Countertop bracket.