Datasheet

NC / NO
The ZR 011 houses two separate thermostats, allowing the independent control of heating and cooling or other
equipment.
Thermostat NC (normally closed):Thermostat opens at temperature rise – for regulating heaters or for switching
signal devices. Comes with red temperature dial.
Thermostat NO (normally open):Thermostat closes at temperature rise – for regulating filter fans and heat
exchangers or for switching signal devices. Comes with blue temperature dial.
> NC / NO or NO / NO in one unit
> Separate adjustable temperatures
> Color coded temperature dials
> DIN rail mountable
Thermostat
ZR 011
e.g. Fan
Wiring examples
Heater
Enclosures heater
Filter fan, cooling equipment, signal device
DUAL THERMOSTAT
ZR 011
Part No. Setting Range Setting Range
01172.0-00 NC - open on rise 0 to +60 °C NO - close on rise 0 to +60 °C
01172.0-01 NC - open on rise +32 to +140 °F NO - close on rise +32 to +140 °F
01175.0-00 NC - open on rise -10 to +50 °C NO - close on rise
+20 to +80 °C
01175.0-01 NC - open on rise +14 to +122 °F NO - close on rise +68 to +176 °F
01176.0-00² NO - close on rise 0 to +60 °C NO - close on rise 0 to +60 °C
01176.0-01² NO - close on rise +32 to +140 °F NO - close on rise +32 to +140 °F
TECHNICAL DATA
Switching difference 12.6 °F ± 7 °F tolerance (7 K ± 4 K)
Sensor element thermostatic bimetal
Contact type snap-action contact
Service life > 100,000 cycles
Max. switching capacity NC: 10 A resistive / 2 A inductive @ AC 250 V
NO: 5 A resistive / 2 A inductive @ AC 250 V
15 A resistive / 2 A inductive @ AC 120 V
DC 30 W (DC 24-72 V)
Max. inrush current AC 16 A for 10 sec.
Connection 4-pole terminal, clamping torque 0.5 Nm max.:
solid wire - AWG 14 max. (2.5 mm²)
stranded wire
1
- AWG 16 max. (1.5 mm²)
Housing plastic, UL 94V-0, light grey
Mounting clip for 35 mm DIN rail, EN 60715
Mounting position vertical
Operating / Storage temperature -49 to +176 °F (-45 to +80 °C)
Operating / Storage humidity max. 95 %RH (non-condensing)
Dimensions 2.6 x 2.0 x 1.8” (67 x 50 x 46 mm)
Weight approx. 3.2 oz. (90 g)
Protection type IP20
Approvals UL File No. E164102, CSA, VDE, EAC (Eurasian Conformity)
¹ When connecting with stranded wires, wire end ferrules must be used.
Important note: The contact system of the regulator is subjected to environmental influences, thus the contact resistance
may change. This can lead to a voltage drop and/or self-heating of the contacts.
² For regulating heat exchangers and fans (e. g. LE 019) and as an alarm contact for monitoring the interior temperature of electronic enclosures.
www.stegousa.com18.02.2016 | Specifications are subject to change without notice. Suitability of this product for its intended use and any associated risks must be determined by the end customer/buyer in its final application.
Toll free: 1-888-783-4611 (US & Canada only) · www.stegousa.com