Instructions / Assembly
1
40271-891-03
03/2005
Lexington, KY, USA
Replaces 40271-891-02 dated 03/2002
Instruction Bulletin
QO
®
Outdoor Load Centers
Class 1130
Retain for future use.
INTRODUCTION
This bulletin contains instructions for the installation and operation of QO
®
outdoor load centers for
Canada manufactured by Schneider Electric.
PREPARATION
1. Determine the wiring or conduit requirements for the
main and branch circuits, as required by local electrical
codes.
2. Select the proper cable clamp, or use other approved
methods for securing the cable or conduit to the
enclosure.
3. Remove the line termination area barrier. See Figure 1.
a. Remove the retaining screws.
b. Remove the barrier. (Barrier must be replaced
before energizing the
load center.)
NOTE: Load centers used in Canada as service
entrance panels must have a barrier between the line
termination and load termination area. All Schneider Electric main circuit breaker load centers
include a factory installed barrier.
DANGER
HAZARD OF ELECTRIC SHOCK, EXPLOSION, OR ARC FLASH
• Apply appropriate personal protective equipment (PPE) and follow safe electrical work practices. See
NFPA 70E.
• This equipment must only be installed and serviced by qualified electrical personnel.
• Turn off all power supplying this equipment before working on or inside equipment.
• Always use a properly rated voltage sensing device to confirm power is off.
• Replace all devices, doors and covers before turning on power to this equipment.
• Do not allow petroleum-based paints, solvents, or sprays to contact the nonmetallic parts of this product.
• Before starting a wiring installation or addition, consult a local building or electrical inspector for current
National Electrical Code requirements. Local codes vary, but are adopted and enforced to promote safe
electrical installations. A permit may be needed to do electrical work, and some codes may require an
inspection of the electrical work.
• This equipment may not be suitable for use in corrosive environments present in agricultural buildings. See
NEC 547 or CEC 2–400.
Failure to follow these instructions will result in death or serious injury.
11003014
Figure 1: Removing the Barrier
Retaining
screws
Barrier
Box
ENGLISH