Brochure

Page 28 – Bulletin 40-10
Liquid Line
Ratings and Selection Recommendations
Replaceable Core Type Refrigerant 407C
NOTE: The variation in flow ratings of filter-driers having the same size core and shell is caused by the difference in connection sizes used. Installing the
secondary filter in C-480 through C-19200 Series shells reduces the flow capacity by approximately 5 percent.
TYPE
SURFACE
FILTERING
AREA
RATINGS AT AHRI STANDARD CONDITIONS SELECTION RECOMMENDATIONS (Tons)
WATER CAPACITY
DROPS AT 60 PPM
REFRIGERANT
FLOW CAPACITY
REFRIGERATION AIR CONDITIONING
Sq.
Inch
cm
2
75°F
25°C
125°F
50°C
Tons at
1 psi ∆P
kW at
0.07 bar ∆P
Commercial
Low Temperature
Equipment
O.E.M.
Self
Contained
Field Replacement
or Field Built-Up
Systems
RCW-42 (High Water Capacity Core)
C-R424-G
67 432 760 245
10.5 36.9 5 7-1/2 5
C-R425-G 12.5 43.9
7-1/2 15 10
C-R427-G 17.0 59.7
RCW-48 or RCW-100 (High Water Capacity Cores)
C-485-G
64 413 934 301
13.5 47.4 10 15 10
C-487-G 22.0 77.2 15 20 15
C-489-G 39.8 139.7 15 30 20
C-967-G
128 826 1868 602
36.1 126.7 25 35 25
C-969-G 44.8 157.2 35 40 35
C-1449-G
192 1239 2802 903
54.6 191.6 40 50 40
C-14411-G 61.7 216.6 50 60 50
C-19211-G
256 1652 3736 1204
77.7 272.7 70 80 70
C-19213-G 91.1 319.8 80 100 80
C-19217-G 95.7 335.9 85 100 85
C-30013-G 294 1897 5716 1844 103 361.5 100 125 100
C-40017-G 392
2529
7621 2458 133 466.8 130 150 130
TYPE
SURFACE
FILTERING
AREA
RATINGS AT AHRI STANDARD CONDITIONS SELECTION RECOMMENDATIONS (Tons)
WATER CAPACITY
DROPS AT 60 PPM
REFRIGERANT
FLOW CAPACITY
REFRIGERATION AIR CONDITIONING
Sq.
Inch
cm
2
75°F
25°C
125°F
50°C
Tons at
1 psi ∆P
kW at
0.07 bar ∆P
Commercial
Low Temperature
Equipment
O.E.M.
Self
Contained
Field Replacement
or Field Built-Up
Systems
RCW-42 (High Water Capacity Core)
C-R424-G
67 432 407 305
11.2 39.3 5 7-1/2 5
C-R425-G 13.4 47.0
7-1/2 15 10
C-R427-G 18.1 63.5
RCW-48 or RCW-100 (High Water Capacity Cores)
C-485-G
64 413 481 361
14.3 50.2 10 15 10
C-487-G 23.3 81.8 15 20 15
C-489-G 42.2 148.1 15 30 20
C-967-G
128 826 962 722
38.3 134.4 25 35 25
C-969-G 47.5 166.7 35 40 35
C-1449-G
192 1239 1443 1083
57.9 203.2 40 50 40
C-14411-G 65.4 229.6 50 60 50
C-19211-G
256
1652
1924 1444
82.4 289.2 70 80 70
C-19213-G 96.6 339.1 80 100 80
C-19217-G 101 354.5 85 100 85
Replaceable Core Type Refrigerant 410A
For suction line
filter-driers
see page 30
For sealed model
Catch-Alls
see page 10