Brochure

Page 18 – Bulletin 40-10
Reversible Heat Pump Filter-Driers
Ratings and Selection Recommendations
For New Installations Refrigerant 22
For Clean-Up After Burnout Refrigerant 22
TYPE
SURFACE
FILTERING AREA
RATINGS AT AHRI STANDARD CONDITIONS
SELECTION
RECOMMENDATIONS
(Tons)
WATER CAPACITY
DROPS AT 60 PPM
REFRIGERANT
FLOW CAPACITY
Sq.
Inch
cm
2
75°F
25°C
125°F
50°C
Tons at
1 psi ∆P
kW at
0.07 bar ∆P
AIR CONDITIONING
HPC-082
15 97 194 158
2.2 7.7
1 thru 3
HPC-082-S
HPC-083
3.7 13.0
HPC-083-S
HPC-084
4.1 14.4
HPC-084-S
HPC-103
18 116 215 176
5.0 17.6
1 thru 5
HPC-103-S
5.5 19.3
HPC-104
8.3 29.1
HPC-104-S
8.9 31.2
HPC-105
10.2 35.8
HPC-105-S
10.8 37.9
HPC-163
26 168 364 297
5.0 17.6
1 thru 8
HPC-163-S
5.5 19.3
HPC-164
8.3 29.1
HPC-164-S
8.9 31.2
HPC-165
10.2 35.8
HPC-165-S
10.8 37.9
HPC-304
53 342 696 567
8.7 30.5
8 thru 20
HPC-304-S
9.3 32.6
HPC-305
9.9 34.7
HPC-305-S
10.5 36.9
HPC-306-S
11.0 38.6
HPC-307-S
11.4 40.0
TYPE
SURFACE
FILTERING AREA
RATINGS AT AHRI STANDARD CONDITIONS
SELECTION
RECOMMENDATIONS
(Tons)
WATER CAPACITY
DROPS AT 60 PPM
REFRIGERANT
FLOW CAPACITY
Sq.
Inch
cm
2
75°F
25°C
125°F
50°C
Tons at
1 psi ∆P
kW at
0.07 bar ∆P
AIR CONDITIONING
HPC-163-HH
26 168 93 81
4.8
16.8
1 thru 8
HPC-163-S-HH
5.2
18.3
HPC-164-HH
7.9
27.7
HPC-164-S-HH
8.5
29.8
HPC-165-HH
9.7
34.0
HPC-165-S-HH
10.3
36.2
HPC-304-HH
53 342 167 119
8.3
29.1
8 thru 20
HPC-304-S-HH
8.8
30.9
HPC-305-HH
9.4
33.0
HPC-305-S-HH
10.8
37.9
HPC-307-S-HH
10.8
37.9