Brochure

Bulletin 40-10 – Page 13
Liquid Line
Ratings and Selection Recommendations
Sealed Type Refrigerant 22
For suction line
filter-driers
see page 30
For replaceable core Catch-Alls see page 21
NOTES: The variation in flow ratings of filter-driers having the same size core and shell is caused by the difference in connection sizes used.
TYPE
SURFACE
FILTERING
AREA
RATINGS AT AHRI STANDARD CONDITIONS SELECTION RECOMMENDATIONS (Tons)
WATER CAPACITY
DROPS AT 50 PPM
REFRIGERANT
FLOW CAPACITY
REFRIGERATION AIR CONDITIONING
Sq.
Inch
cm
2
75°F
25°C
125°F
50°C
Tons at
1 psi ∆P
kW at
0.07 bar ∆P
Commercial &
Low Temperature
Equipment
O.E.M.
Self
Contained
Field Replacement
or Field Built-Up
Systems
C-032
9 58 61 50
1.5 5.3
1/4 1 1/2
C-032-CAP
C-032-S
C-032-F
C-032-FM
C-033 3.5 12.3
C-033-S 3.8 13.3
C-052
15 97 146 119
2.1 7.4
1/3 1 thru 3 3/4 thru 2
C-052-S
C-052-F
C-052-FM
C-0525-S 3.4 11.9
C-053 4.1 14.4
C-053-S 4.7 16.5
C-082
21 135 240 196
2.1 7.4
1/2 thru 1-1/2 1 thru 5 1 thru 2
C-082-S
C-0825-S 3.7 13.0
C-083 4.5 15.8
C-083-S 5.2 18.3
C-084 8.1 28.4
C-084-S 8.7 30.5
C-162
33 213 364 297
2.1 7.4
1-1/2 thru 3 2 thru 10 1-1/2 thru 5
C-162-S
C-1625-S 3.7 13.0
C-163 4.5 15.8
C-163-S 5.2 18.3
C-164 10.1 35.5
C-164-S 11.0 38.6
C-165 12.1 42.5
C-165-S 13.8 48.4
C-303
53 342 696 567
4.6 16.1
3 thru 5 5 thru 20 4 thru 10
C-303-S 5.3 18.6
C-304 10.1 35.5
C-304-S 11.0 38.6
C-305 14.9 52.3
C-305-S 16.9 59.3
C-307-S 21.6 75.8
C-414
67 432 936 763
11.5 40.4
5 thru 12
7-1/2
thru 23
7-1/2 thru 15
C-414-S 12.4 43.5
C-415 15.8 55.5
C-415-S 17.5 61.4
C-417-S 22.1 77.6
C-419-S 24.3 85.3
C-607-S
106 684 1392 1134
29.1 102.1
15 25 thru 30 20
C-609-S 33.2 116.5