Brochure

Page 36 – Bulletin 40-10
Compact Stye
Suction Line Filter-Driers
TYPE
REFRIGERANT
SELECTION
RECOMMENDATIONS
HORSEPOWER
134a 22 407C 410A
EVAPORATOR TEMPERATURE °F
0 20 40 -40 -20 0 20 40 40 40 REFRIGERANT
PRESSURE DROP – psi
22, 407C
& 410A
12, 134a, 404A,
502 & 507
1 1-1/2 2 1/2 1 1-1/2 2 3 3 3
C-144-S-TT-HH 0.5 0.8 1.3 0.2 0.4 0.9 1.3 2.2 2.1 2.7 2 1
C-145-S-TT-HH 0.8 1.3 2.1 0.4 0.8 1.4 2.2 3.6 3.5 4.6 3 2
C-146-S-TT-HH 1.1 1.8 2.9 0.6 1.2 2.0 3.0 4.9 4.8 6.2 3 2
C-147-S-TT-HH 1.3 2.1 3.2 0.7 1.3 2.2 3.3 5.4 5.3 6.8 5 3
C-149-S-TT-HH 1.6 2.7 4.2 0.9 1.7 2.9 4.4 7.1 7.0 9.0 5 3
PROVEN BENEFITS:
Short overall length, suitable for
cramped piping situations — shorter
than other similar type filter-driers.
Suitable for use on 1 through 5 ton air
conditioning systems, with suction line
sizes in the range of 1/29 to 1-1/89. Also
applicable on the common suction line
of heat pump systems.
The famous Sporlan HH core
removes all types of contaminants
including moisture, acid, dirt, and
sludge. A blend of two desiccants, plus
activated charcoal, gives maximum
performance.
Access valves permit measuring the
pressure drop across the filter-drier
during clean-up, following a hermetic
motor burnout.
application
The short overall length of these filter-
driers permit easy installation, even on
systems with restricted space. While
designed for the minimum possible
overall length, these filter-driers are suit-
able for use on most air conditioning
systems. The filter-drier has two access
valves for measuring the pressure drop
across the filter-drier core during the
clean-up process.
Heat pump systems frequently have
cramped piping in the very compact
cabinet. The C-140 Series Catch-All is not
a reversible filter-drier, therefore it must
be installed in the common suction
line. The service technician needs a
short suction line filter-drier to fit in
this restricted space. The C-140 Series
Catch-All meets this essential need.
constrUction
The core is held in place by a leaf spring
at the inlet end. Filtration occurs on the
core surface, and a 100 mesh screen is
used as a safety filter at the outlet end.
The screen and core are sealed to the
shell wall with a fiberglass pad. The
Type C-144-S-TT-HH through C-149-S-TT-HH
Maximum Rated Pressure of 650 psi / 44.8 bar
B B
A
INLET
Volume of desiccant is 14 cubic inches (229 cm
3
). Filtering area is 27 square inches (174 cm
2
).
C
UL
US
Recognized Component — Guide-SMGT2-File No. SA-1756.
TYPE
CONNECTION
SIZE
Inches
ODF Solder
OVERALL
LENGTH
“A”
SOLDER
SOCKET DEPTH
“B”
DIAMETER
OF BODY
SHIPPING
WEIGHT
Inches mm Inches mm Inches mm lb kg
C-144-S-TT-HH 1/2 4.14 105 .50 13
4.44 113 2.0 0.9
C-145-S-TT-HH 5/8 4.38 111 .62 16
C-146-S-TT-HH 3/4 4.83 123 .69 18
C-147-S-TT-HH 7/8 4.97 126 .75 19
C-149-S-TT-HH 1-1/8 4.93 125 .96 24
Specifications
threaded valve core for each access valve
is supplied in a separate envelope. This
way the heat sensitive valve core can be
installed after brazing the Catch-All into
the line. The Catch-All utilizes copper
connections for ease in brazing with any
type of alloy.
While designed for use in the suction
line these filter-driers may be installed in
the liquid line, if desired under unusual
circumstances. The performance of these
filter-driers in the liquid line is similar
to the popular C-160 Series Catch-All
Filter-Driers.
Flow Capacity* Tons
°F
psi
Rated in accordance with ANSI/AHRI Standard 730.
TYPE
REFRIGERANT
SELECTION
RECOMMENDATIONS
HORSEPOWER
134a 22 407C 410A
EVAPORATOR TEMPERATURE °C
-20 -5 0 -40 -30 -20 -5 5 5 5 REFRIGERANT
PRESSURE DROP – bar
22, 407C
& 410A
12, 134a, 404A,
502 & 507
0.07 0.10 0.14 0.03 0.07 0.10 0.14 0.21 0.21 0.21
C-144-S-TT-HH 1.8 2.8 4.6 0.7 1.4 3.2 4.6 7.7 7.4 9.5 2 1
C-145-S-TT-HH 2.8 4.6 7.4 1.4 2.8 4.9 7.7 12.6 12.3 16.1 3 2
C-146-S-TT-HH 3.9 6.3 10.2 2.1 4.2 7.0 10.5 17.2 16.8 21.8 3 2
C-147-S-TT-HH 4.6 7.4 11.2 2.5 4.6 7.7 11.6 19.0 18.6 23.9 5 3
C-149-S-TT-HH 5.6 9.5 14.7 3.2 6.0 10.2 15.4 24.9 24.6 31.6 5 3
Flow Capacity* kW
°C
bar
*The water capacity and acid capacity of the C-140 Series are comparable to the popular C-160-S-T-HH Series Filter-Drier.
Specific values are not listed since the industry has no standard method for testing the water capacity or acid removal ability
in the suction line of refrigerant systems. The flow capacity information above permits selecting C-140 Series Catch-Alls for
various conditions with confidence.